SECTION 9. INPUT/OUTPUT INSTRUCTIONS
9-28
TABLE 9-10. Extended Vibrating Wire
Range Codes
Range
Peak to Peak Volts
Maximum
Code
Required @ Max. Freq.*
Frequency
1
2 mV
10 kHz
2
5 mV
20 kHz
3
20 mV
30 kHz
4
500 mV
100 kHz
PARAM
DATA
NUMBER
TYPE
DESCRIPTION
01:
2
Repetitions (Index (- - )
to skip repeat of
excitation)
02:
2
Range Code (Table 9-10)
03:
2
Single-ended channel
for first measurement
04:
2
EX CHAN
05: 4
Starting
Frequency
(HZ)
06:
4
Ending Frequency (HZ)
07:
4
T (sweep, Units = 1
msec)
08:
4
N (Number of steps)
09:
4
Delay after excitation
before measurement
(Units = 0.01 sec)
10:
4
CYCLES to measure
11:
4
DELAY between reps
(Units = 0.01 sec)
12:
4
First Input Location
13:
FP
Multiplier
14:
FP
Offset
Input Locations Altered: 2 per repetition
*** 132 INPUT SETTLING TIME ***
Instruction P132 allows a user to change the
default 450
µ
s input voltage settling time for
Instructions P1, P2, P5, P6, P7, P9, P11, P13,
and P14. Measurement errors will result if
insufficient input settling time exists for a given
sensor and cable length (see Section 13.3). The
minimum allowable settling time for P132 is 100
µ
s for all input ranges except the
±
10 mV range,
in which 200
µ
s is the minimum. The maximum
allowable settling time is 6 ms. An entry of 0.0000
ms results in the default 450
µ
s input settling
time. High-output impedance (> 1 k
Ω
) sensors
and / or long cable lengths may require more
than the 450
µ
s default settling time. Low-output
impedance sensors and / or short cable lengths
may require less settling time. A single P132
instruction in the datalogger program will change
all applicable default settling times. Multiple
P132 instructions in a datalogger program will
cause settling time changes for the analog
measurement instructions following each P132.
Shortened settling times for the P10 and P17
instruction will degrade the measurement
accuracy, while longer times will increase the
time required to perform the instructions. A P132
within a scan does not over-ride the settling
times in the P4 and P8 instruction; instead it adds
to this time. If P132 is used in the program,
P4,
P8, P10, and P17 Instructions should be
preceeded by a P132
to set the settling time
back to the desired 450
µ
s (time 0.0000).
Performing P132 instructions within a scan
increases the time to execute the scan by 0.13
ms per P132 instruction. This needs to be
considered when using the P132 instruction to
reduce the time required to complete a scan.
P132 in Table 1 will not affect measurements in
Table 2. The reverse is also true.
PARAM.
DATA
NUMBER
TYPE
DESCRIPTION
01:
FP
milliseconds
Minimum = 0.2 for X1
Range codes, else
Minimum range is 0.1.
Maximum = 6.0 ms.
0 = default = 450
milliseconds
Input Locations Altered = 0
*** 133 Continuous Analog Out ***
Sets a continuous analog output port to a
voltage level specified in an input location. The
analog output degrades approximately 0.17mV
every 7 seconds requiring the instruction to be
periodically repeated to maintain a given output
accuracy.
mA
mA
Port
Source
Sink
Option
Description
(+V)
(-V)
01 - 02
CAO1 & CAO2
15
5
11 - 12
CAO1 & CAO2
15
15
with Boost
Содержание CR23X
Страница 8: ...CR23X TABLE OF CONTENTS vi This is a blank page ...
Страница 12: ...CR23X MICROLOGGER OVERVIEW OV 2 1 2 3 A 4 5 6 B 7 8 9 C 0 D FIGURE OV1 1 CR23X Micrologger ...
Страница 34: ...CR23X MICROLOGGER OVERVIEW OV 24 This is a blank page ...
Страница 50: ...SECTION 1 FUNCTIONAL MODES 1 16 This is a blank page ...
Страница 72: ...SECTION 4 EXTERNAL STORAGE PERIPHERALS 4 8 This is a blank page ...
Страница 88: ...SECTION 6 9 PIN SERIAL INPUT OUTPUT 6 10 This is a blank page ...
Страница 103: ...SECTION 7 MEASUREMENT PROGRAMMING EXAMPLES 7 15 CR23X AVW1 FIGURE 7 15 2 Well Monitoring Example ...
Страница 110: ...SECTION 7 MEASUREMENT PROGRAMMING EXAMPLES 7 22 This is a blank page ...
Страница 134: ...SECTION 8 PROCESSING AND PROGRAM CONTROL EXAMPLES 8 24 This is a blank page ...
Страница 164: ...SECTION 9 INPUT OUTPUT INSTRUCTIONS 9 30 This is a blankpage ...
Страница 188: ...SECTION 11 OUTPUT PROCESSING INSTRUCTIONS 11 8 This is a blankp age ...
Страница 221: ...SECTION 13 CR23X MEASUREMENTS 13 21 FIGURE 13 5 1 Circuits Used with Instructions 4 9 ...
Страница 229: ...14 3 1 2 3 A 4 5 6 B 7 8 9 C 0 D FIGURE 14 3 1 CR23X Battery Pack and Panel ...
Страница 239: ...SECTION 14 INSTALLATION AND MAINTENANCE 14 13 S A N Y O FIGURE 14 11 6 Removal of band clamp and battery ...
Страница 240: ...SECTION 14 INSTALLATION AND MAINTENANCE 14 14 This is a blank page ...
Страница 244: ...APPENDIX A GLOSSARY A 4 This is a blank page ...
Страница 268: ...APPENDIX B CONTROL PORT SERIAL I O INSTRUCTION 15 B 24 This is a blank page ...
Страница 276: ...APPENDIX C BINARY TELECOMMUNICATIONS C 8 This is a blank page ...
Страница 278: ...This is a blank page ...
Страница 282: ...APPENDIX F DYNAGAGE SAP FLOW P67 F 4 This is a blank page ...
Страница 299: ...APPENDIX I TD OPERATING SYSTEM ADDENDUM FOR CR510 CR10X AND CR23X MANUALS ...
Страница 300: ...This is a blank page ...
Страница 302: ...This is a blank page ...
Страница 308: ...TABLE DATA ADDENDUM AD 6 This is a blank page ...
Страница 324: ...TD ADDENDUM SECTION 1 FUNCTIONAL MODES AD 1 8 This is a blank page ...
Страница 340: ...TD ADDENDUM SECTION 8 PROCESSING AND PROGRAM CONTROL EXAMPLES AD 8 10 This is a blank page ...
Страница 342: ...This is a blank page ...
Страница 373: ...This is a blank page ...