PM 1001812 000 00
Device handbook SIRAX BM1450
8/36
4.3 Commissioning
Before commissioning you have to check if the connection data of the device match the data of the plant.
If so, you can start to put the device into operation by switching on the power supply and the measurement inputs.
It is to be noted, that the data given on the type plate are respected!
ORDER CODE: 177065
SR No.: 16/12/0001
SIRAX BM1450
AUXILIARY: 60..300V AC/DC, 6.0VA
CLASS: 1.0
CURRENT INPUT: 4 CH, 50...150mV
V3.02
OPTION: RS485 + 4Relay
!
VOLTAGE INPUT: 1 CH, 10...60VDC
Label version standard
4.3.1 Operating the device
The following values of the SIRAX BM1450 can be configured and
programmed on site: voltage input, current input, shunt setting range,
number of channels and demand integration time.
There are three buttons on the front panel that allow the user to navigate
through the available measured values (instantaneous values, energy,
and min./max.) and to configure the device.
Operation is performed by means of 3 keys:
•
3 keys “
UP”, “
DOWN” and "OK" for navigation and for the
selection of values.
4.3.2 LED indications
The LED indicators are used for various purposes. They change color according to their status.
In the setup menu
LED
Operating condition
green
Display of the channel to be parameterized
In display mode
LED
Operating condition
green
Normal operation (good condition)
red
Overload condition
In display mode with limit relay
LED
Operating condition
green
Normal operation (good condition)
red
Alarm condition available
Down
Up
Enter key
LED Channel
(Grün & Rot)
LED Parameter
LED
Multiplier
In the display mode with derived parameters (power, energy, amp
hours)
LED
Operating condition
green
Voltage and current in normal operation (good condition)
red
If one of the parameters is in overload condition
red
For limit assignment in the alarm state
green
With limit assignment normal operation (state good)
When more than one from the above conditions are applicable, the LEDs will
follow "OR" logic for alarm condition and "AND" logic for healthy condition,
i.e. it will glow red when even one of the alarm conditions is true and it will
only glow green when all of the healthy conditions are true.