Device handbook SIRAX BM1450
33/36
Table 13: Reset Parameter
Parameter No Parameter
Parameter No Parameter
Parameter No Parameter
0
None
5
Low voltage
12XXXX
Ampere hour
1
All
6XXXX
High current
13XXXX
Run hour
2
On hour
7XXXX
Low current
14XXXX
Channel data
3
No of interrupts
8XXXX
Energy
4
High votage
9XXXX
Demand
For reset parameters, XXXX represents channels 1, 2, 3 & 4. To reset a parameter on a particular channel, write 1 instead of the X otherwise
write 0. For example, if a user wants to reset channels 1 and 2, the reset code is 81100..
Table 14: Communication Parameters
Baud Rate Parity
Stop
bit
Decimal
value
Baud Rate Parity
Stop
bit
Decimal
value
Baud Rate Parity
Stop
bit
Decimal
value
4800
None
1
0
9600
Odd
1
7
38400
Even
1
14
4800
None
2
1
19200
None
1
8
38400
Odd
1
15
4800
Even
1
2
19200
None
2
9
57600
None
1
16
4800
Odd
1
3
19200
Even
1
10
57600
None
2
17
9600
None
1
4
19200
Odd
1
11
57600
Even
1
18
9600
None
2
5
38400
None
1
12
57600
Odd
1
19
9600
Even
1
6
38400
None
2
13
Table 15: Relay Configuration
A) For Limit Relay
B) For Timer, Reverse Lock Relay
Code
Configuration
Code
Configuration
0
Hi - alarm & energised Relay
0
Energize when triggered
1
Hi - alarm & De-energised Relay
1
De-energize when triggered
2
Lo - alarm & Energised Relay
3
Lo - alarm & De-energised Relay
Table 16: Number of Cycles for Timer Relay
Code
Configuration
0
Unlimited
1...9999 Fixed Cycles
10.3 User Assignable Modbus Registers
The SIRAX BM1450 contains 20 user assignable registers in the address range of 0x200 (30513) to 0x226 (30551) for 3X registers (see Table
17) and address range of 0x1E00 (47681) to 0x1E26 (47719) for 4X registers (see Table 18).
Any of the parameter addresses (3X register addresses and 4X register addresses Table 10) accessible in the instrument can be mapped to these
20 user assignable registers.
Parameters (3X and 4X registers addresses) that reside in different locations may be accessed by the single request by re-mapping them to
adjacent address in the user assignable registers area.
The actual address of the parameters (3X and 4X registers addresses) which are to be accessed via address 0x200 to 0x226 (or 0x1E00 to
0x1E26) are specified in 4X Register 0x200 to 0x213. (see TABLE 19)