P
age
23
- Manual
FA01610-EN
- 08/2021 - © C
AME S.p.A. - The contents of this manual may be changed at any time and without notice. - T
ranslation of the o
riginal instructions
Opening speed
Set the opening speed (percentage of maximum speed).
The percentage values automatically adapt to the value entered in the function [Boom length].
Configuration>
Gate travel settings
Opening speed
50% to 100% (Default 70%)
Closing speed
Set the closing speed (percentage of maximum speed).
The percentage values automatically adapt to the value entered in the function [Boom length].
Configuration>
Gate travel settings
Closing speed
from 30% to 100% (Default 50%)
Travel sensitivity
Adjust the obstruction detection sensitivity during boom travel.
Configuration>
Gate travel settings
Travel sensitivity
10% to 100% (Default 100%)
Total stop
This stops the boom and excludes automatic closing. Use a control device to resume movement.
Configuration>
Wired safety devices
Total stop
Deactivated (Default)
On
CX input
Associate a function with the CX input.
Configuration>
Wired safety devices
CX input
Deactivated (Default)
C1 = Reopen while closing (photocells)
C4 = Obstacle standby (photocells)
C5 = Immediate closure at the travel end during opening
C7 = Reopen while closing (sensitive edges)
C9 = Immediate closure at the travel end during opening with obstacle standby during
closure
C10 = Immediate closure during opening with obstacle standby during closure
C13 = Reopening during closure with immediate stop once the obstacle has been
removed, even with boom not in movement
r7 = Reopen while closing (sensitive edges with 8K2 resistor)
CY input
Associate a function with the CY input.
Configuration>
Wired safety devices
CY input
Deactivated (Default)
C1 = Reopen while closing (photocells)
C4 = Obstacle standby (photocells)
C5 = Immediate closure at the travel end during opening
C7 = Reopening during closure (sensitive edges)
C9 = Immediate closure at the travel end during opening with obstacle standby during
closure
C10 = Immediate closure during opening with obstacle standby during closure
C13 = Reopening during closure with immediate stop once the obstacle has been
removed, even with boom not in movement
R7 = Reopening during closure (sensitive edges with 8K2 resistor)