Cable types and minimum thicknesses
CABLE LENGTH (m)
< 10
10 to 20
from 20 to 30
Power supply 230 V AC
3G x 1.5 mm²
3G x 1.5 mm²
3G x 2.5 mm²
24 V AC - DC Flashing beacon
2 x 1 mm²
2 x 1 mm²
2 x 1 mm²
TX Photocells
2 x 0.5 mm²
2 x 0.5 mm²
2 x 0.5 mm²
RX photocells
4 x 0.5 mm²
4 x 0.5 mm²
4 x 0.5 mm²
Command and control devices
*no. x 0.5 mm²
*no. x 0.5 mm²
*no. x 0.5 mm²
Antenna
RG58 max 10 m
* no. = see product assembly instructions - Warning: the cable cross-section is indicative and varies according to the motor power and cable length.
For installation in an outdoor environment, use cables with properties at least equivalent to those of type H05RN-F (with designation 60245 IEC 57).
For installation in an indoor environment, use cables with properties at least equivalent to those of type H05VV-F (designation to 60227 IEC 53).
If the cable lengths differ from those specified in the table, define the cable cross-sections according to the actual power draw of the connected devices
and in line with regulation CEI EN 60204-1.
For multiple, sequential loads along the same line, recalculate the values in the table according to the actual power draw and distances. For information
on connecting products not covered in this manual, please see the documentation accompanying the products themselves.
For paired and CRP connection, use a UTP CAT5 cable. Maximum length 1000 metres.
Wind resistance
The table shows the boom wind-load resistance.
Resistance class with reference to the EN 13241 standard.
Type
Boom 2.25 m
Boom 3.05 m
Boom 4.05 m
Resistance class
5
4
3
Wind pressure [Pa]
1200
1000
800
Maximum wind speed [km/h]
144
132
118