CX-DE1200 Delayed Egress Electro Magnetic Lock
INSTALLATION INSTRUCTIONS
Pwr
NO C NC
Fire P
C NC
Lock
Grn Rly
Red Rly
Ex-Trig Reset
R-Exit Bypass
Ex-Spkr
DPS
Bond-S
ATS
ON
DIP
1 2 3 4 5 6 7 8
NO C NC NO C NO C NO C NO C
NO C NC NO C NC
NO C NC
J10
Pwr
Remove
this J10 jumper only if Fire P
anel
or Smoke Detection system is connected to the (Fire P) terminal.
External Speaker
8Ω, 1.5W (Optional)
CM-1200
Key Switch
(Optional)
Mode: 15 and 30 Seconds
Door armed and locked in 15 or 30 seconds mode
Mode: Bypass
Door unlocked (Either Bypass or R-exit)
Mode: Bypass
Installed: Factory default setting
Jumper J10 (Fire
Panel
Input)
Uninstalled: Only if a dry contact (NC) from a
fire alarm p
anel
or smoke
detector system is connected to
the
“Fire P” terminals.
Door unlocked & alarm sounding until reset
Display Mode
Jumper Settings
Push Bar (Optional)
CM-120i Keypad
(optional)
AC Main
Fire Panel
2 Core Cable
3 Core Cable
Power Supply
Push Bar (Ex-Trig)
Keypad
Key Switch
Built-In
Key Switch
(Reset &
Bypass)
NO
NO
COM
COM
AUX Rly
Main Rly
NO
COM
GND
+12V
Lock Output not
to be used for
model CX-DE1200
Single Door Configuration
NOTE:
1) all field-wiring to the unit
shall not exceed 30 m (98.5 ft)
in length.
2) all external power sources
shall be UL Listed with Class 2,
power-limited output.
Optional direct passthrough
for CX-DE1201 tandem lock
(Manual Reset
Or Bypass)