CX-DE1200 Delayed Egress Electro Magnetic Lock
INSTALLATION INSTRUCTIONS
6. ARMATURE MOUNTING INSTRUCTIONS
Out Swing
DE1200-TEMPLATE with FB-DE1200-280
FOLD 90° ON THIS DOTTED LINE
Note: Dimensions might change if photocopied.
Place Against
Door Frame
FB-DE1200 Template
Drill 1/2"
Dia. for Cable
Access Hole
Install the mounting plate at 2
slots position first, then make
proper adjustment before
marking remaining screws
hole position.
Armature Housing-DE1200 Template
Place Against Door
Install the Armature Housing
with 2 screws position
first, then make proper
adjustment before marking
remaining screws hole position.
IG-DE1200-280 Ver.1019
Out-Swing
Door Only
Door Frame
Door Frame
Door Frame
Door Frame
Armature Plate
Armature Housing
Temporary mount with self tapping screw
EZ Interlocking
Mounting Plate
Screw #2
Screw #1
2.
Drill mark the
screw hole
according to the
template holes
(Door & Frame)
Mounting Template
Door
1”
Door
Door
Door
Spring
Armature Screw
Proxy
Trigger
Door
Step 1:
Close the door, position the EM lock mounting location as close to the upper corner of the door with a minimum gap 1".
Step 2:
Place the template against the door and frame and drill holes according to template indications.
Step 3:
Place the mounting plate against the door frame and screw in according to the template holes position.
Step 4:
Place the armature housing against the door and screw in according to the template holes position