PMP Synchronization Solutions User Guide
Installing a CMM4
PMP-0297 007v001 (January, 2017)
3-56
Figure 56 Rackmount CMM line filter installation (EU only)
3
Using spade lugs, connect the DC cables from the CMM DC input
screw terminals to the “Load” side of the filter.
•
(29V installations) The length of 14 AWG or 16 AWG
cabling between the CMM and filter should be 10.5 in +/-
0.5 in (27 cm +/- 1 cm) .
•
(56V installations) The length of 14 AWG or 16 AWG
cabling between the CMM and filter should be 11.5 in +/-
0.5 in (29 cm +/- 1 cm)
4
Using spade lugs, connect the DC cables from the power supply to
the “Line” side of the filter. The filter has no DC polarity, ensure
that polarity is maintained on the wiring going through the filter
(for example, the posititive wire must be connected to the same-
side terminal on the “Line” and “Load” sides of the filter. Refer to
Table 9 Wire size for CMM4 DC cable
recommendations.
5
Once the filter is secured and the wiring is connected, main power
may be restored.