AFX SERIES® OPERATION MANUAL
SECTION 6:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS)
• All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 134 of 402
UNIT CONFIGURATION 2 OF 2 ----------------------------------------------------------------------------------
Allow Output Enable at Power On
This mode if set, causes the output to turn on at
power up.
Enable Current Overload
Current Overload mode allows the power source to provide
more than the nominal max. RMS current (around 30
percent more) for a short period (up to 2 seconds). When
enabled, the user can set the CURR:LIM 30% higher than
whit this mode off. For example in a stand-alone 3150AFX
unit in three phase mode (FORM 3), RMS output current
can be up to 55A when the continuous output limit is 41.7A.
A warning message will be display notifying the user this
mode is being enabled.
Recall last settings at power-on When checked, this mode will cause the last settings that
were in effect when the power source was last turned off to
be recalled at power on. This allows a user to resume
operation without having to set up again between power
on/off events.
Positive phase rotation
When checked, the phase rotation in three phase mode will
be set to A -> C -> B corresponding to positive phase
rotation for three phase AC motors. To select negative
phase rotation, uncheck this option.
Access to other utility screens is available from the UNIT CONFIGURATION screen through
the soft keys. The table below lists the available soft keys on the UNIT CONFIGURATION
screen.
SOFT KEY
Description
Transient Settings (SK1)
Display Transient Configuration Settings
Output Impedance (SK2) Program Output Impedance R and L values.
User Presets (SK3)
Access to user defined preset value settings for output
programming soft keys
Next Screen (SK5)
Toggle to alternate UNIT CONFIGURATION screen
Table 6-16: Available UNIT CONFIGURATION 2 screen soft keys