AFX SERIES® OPERATION MANUAL
SECTION 8:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS)
• All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 245 of 402
Command Syntax
[SOURce:]VOLTage:DC#
Description
Sets DC voltage for phase #. If # is omitted, sets all available phases to
value specified.
Note: Source must be in DC or AC+DC mode and UPC compatibility
mode must be disabled.
Parameters
Range 0.0000 - 425.0000
Parameter Format
<nr2>
Example
VOLT:DC1 375.0
Query Format
[SOURce:]VOLTage:DC#?
Returned Data Format
<nr2>
Query Example
VOLT:DC1?
375.0000
Command Syntax
[SOURce:]VOLTage:DC#:SLEW
Description
Sets DC voltage slew rate for phase #. If # is omitted, sets all available
phases to value specified.
Note: Source must be in DC or AC+DC mode and UPC compatibility
mode must be disabled.
Parameters
Range 0.01- 850.00
Parameter Format
<nr2> and <nr3>
Example
VOLT:DC1:SLEW 850.00
Query Format
[SOURce:]VOLTage:DC#:SLEW?
Returned Data Format
<nr2>
Query Example
VOLT:DC1:SLEW?
850.0000
Command Syntax
[SOURce:]VOLTage:DC#:LIMit:MINimum
Description
Sets low user limit for DC voltage programming for phase #. If # is
omitted, sets all available phases to value specified. User limits must
fall within actual hardware limits of the power source. Also, MIN limit
must be less than MAX limit.
Parameters
-425.0 – 425.0
Parameter Format
<nr2>
Example
VOLT:LIM:DC1:MIN 20.0
Query Format
[SOURce:]VOLTage:DC#:LIMit:MINimum?
Returned Data Format
<nr2>
Query Example
VOLT:DC1:LIM:MIN?
-425.000