WALL -TILE - MOON - LEAN

4

3.3 

SMOKE DUCT (SMOKE FITTING)

The smoke duct is the pipe that connects the appliance to the flue. 

This smoke fitting must comply in particular with the following requirements:

•  comply with product standard EN 1856-2; 

•  its cross-section must be of constant diameter and no less than that of the appliance outlet, from the firebox outlet up to the 

connection in the flue;

•  the horizontal section must be as short as possible and extend no more than 4 metres;

•  the horizontal sections must have a minimum upward slope of 3%; 

•  changes of direction must have an angle no greater than 90° and be easy to inspect

•  the number of changes of direction, including that for entry into the flue, and exclusion of the T in the event of a side or rear 

outlet, must not exceed 3; 

•  it must be insulated if it passes outside the installation room

•  it must not in any case cross rooms in which it is forbidden to install combustion appliances.

•  the use of flexible metal and fibre cement or aluminium hoses is forbidden;

In any case, smoke ducts must be sealed against combustion products and any condensation. For this reason, it is recommended 

to use pipes with silicone gaskets or similar sealing devices that withstand the operating temperatures of the appliance (e.g. T200 

P1) and that by removing the gaskets, are still T400 N1 G certified.

SYSTEM TYPE

Ø80 mm PIPE

Ø100 mm PIPE

Minimum vertical length

1,5 mt

2 mt

Maximum length (with 1 union)

6,5 mt

10 mt

Maximum length (with 3 unions)

4,5 mt

8 mt

Maximum number of unions

3

3

Level section (minimum inclination 3%)

4 mt

4 mt

Installation at a height above 1200 m a.s.l.

NO

Obligatory

3.4 

FLUE (CHIMNEY OR PIPED DUCT)

When creating the flue, in particular comply with the following requirements:

•  comply with the applicable product standard (EN 1856, EN 1857 EN 1457, EN 1806, EN 13063..); 

•  be made with suitable materials to ensure resistance to normal mechanical, chemical, thermal stresses and have adequate 

thermal insulation in order to limit the formation of condensate; 

•  have a predominantly vertical configuration and be free of choke points along its entire length; 

•  be correctly spaced by air gaps and isolated from combustible materials; 

•  the flue inside the house must still be insulated and can be inserted in an air shaft provided it complies with the regulations 

for piping; 

•  the smoke duct must be connected to the flue by means of a Tee fitting with an inspectable collection chamber for the collec-

tion of soot and any condensate.

•  where the sizing provides for wet operation, a suitable condensate collection and siphon discharge system must be set up.

We recommend checking the data plates of the flue for the safety distances that must be observed in 

the presence of combustible materials and, if necessary, the type of insulating material to be used.  

It is forbidden to connect the stove to a collective or shared flue

 

with other combustion appliances or 

with hood outlets. 

It is forbidden to use the direct drain on the wall or towards indoor spaces and any other form of drain 

not provided for by the regulation in force in the country of installation.

Содержание WALL3 PLUS

Страница 1: ...INSTALLER MANUAL Pellet Stove EN WALL3 PLUS TILE3 PLUS MOON LEAN3 PLUS 2022CADELsrl Allrightsreserved Tuttiidirittiriservati new...

Страница 2: ...Specialized Stove repairer WARNING symbols indicates an important note 2 PACKAGING AND HANDLING 2 1 PACKAGING ThepackagingismadeupofrecyclablecardboardboxesaccordingtoRESYstandards recyclableexpandedp...

Страница 3: ...with the utmost care 3 CHIMNEY FLUE 3 1 PREPARING THE SMOKE EXPULSION SYSTEM The combustion product expulsion system is a particularly important element for the proper operation of the appliance and...

Страница 4: ...5 mt 10 mt Maximum length with 3 unions 4 5 mt 8 mt Maximum number of unions 3 3 Level section minimum inclination 3 4 mt 4 mt Installation at a height above 1200 m a s l NO Obligatory 3 4 FLUE CHIMN...

Страница 5: ...the internal section of the chimney prevent the penetration of rain or snow ensure the outlet of smoke even in the event of wind windproof chimneypot the height of outflow must be beyond the reflux a...

Страница 6: ...stallation room can take place with a free air inlet or by channelling the air directly to the outside The free air inlet must be made at floor level always be protected with an outer grille and in su...

Страница 7: ...corrugated duct 50 mm 60 mm 1 m 80 mm 3 m 1 m 100 mm 7 m 4 m Fig 7 Directairinflow Fig 8 Airinletforsealed chamberinstallation LEGEND Fig 7 Fig 8 1 Roomtoventilate 2 Externalairinlet 4 Shieldgrid 5 Cu...

Страница 8: ...height for the installation of a vertical exhaust flue roof HV 6 mt see Fig 13 Maximum height for the installation of a horizontal exhaust flue wall HO 2 6 mt see Fig 13 Fig 11 Flexibletube Fig 12 Con...

Страница 9: ...cases install suitable insulation between the flue and the ceiling Always check and comply with the plate data of the flue specifically the minimum safety distances from combustible materials The pre...

Страница 10: ...13384 1 which is resistant to soot fire and which complies with the distances prescribed by the combustible materials indicated on the plate data there is a suitable combustion air flow to the applian...

Страница 11: ...as furniture curtains or sofas as a precaution increase the stove clearances substantially to avoid possible deterioration due to the effect of heat Fig 15 Safetydistancesfromcombustiblematerial LEGEN...

Страница 12: ...ark DK BEK n 541 del 27 04 2020 6 3 WALL MOUNTING The stove is suitable for wall mounting The can be attached to a load bearing wall in masonry NOT plasterboard wood etc suitable for the entire weight...

Страница 13: ...air inlet hole To fix the rear support to the wall with metal plugs su1itable for the weight of the stove see Fig 18 Fig 18 Mountingonflammablewall LEGEND WALL3 PLUS LEAN3 PLUS MOON 1 833 mm 833 mm 83...

Страница 14: ...SIONS Fig 20 Generaldimensions Wall3 Plus LEGEND Fig 20 1 96 3cm 2 100 5cm 3 27 7cm 4 82 8cm 5 17 2cm 6 87 7cm 7 17 1cm 8 15 9cm 9 8 3cm 10 87 5cm 11 13 5cm 12 13 5cm 13 30 5cm 14 29cm 15 Ductingoutle...

Страница 15: ...Plus LEGEND Fig 21 1 93cm 2 117 5cm 3 25cm 4 85 5cm 5 8cm 6 89 5cm 7 17 2cm 8 10 5cm 9 8 3cm 10 89 5cm 11 7 5cm 12 7 5cm 13 46 5cm 14 32 5cm 15 27 3cm 16 Ductingoutletd 8cm 17 Holecombustionairinletd...

Страница 16: ...2cm 12 13 2cm 13 28cm 14 28 4cm 15 Ductingoutletd 8cm 16 Holecombustionairinletd 6cm 17 Exhaustfumesd 8cm Fig 23 Generaldimensions Tile3 Plus LEGENDA Fig 23 1 94 8cm 2 110 8cm 3 28 8cm 4 12 6cm 5 11c...

Страница 17: ...Keep the door in a safe place until next use Fig 24 Removescrews Fig 25 Doorremoval DOOR ASSEMBLY To assemble the door you must centre the pivots fixed to the door on the structure bracket After havi...

Страница 18: ...e teeth screws in the appropriate slots and making them lower to the bottom see Fig 28 and Fig 29 Fix the lower part of the panels with the screws see Fig 30 6 9 PANEL ASSEMBLY MOON MODEL Assemblymust...

Страница 19: ...d lower coating union brackets from the magnets Compose the coating by fixing the 2 coloured panels to the 2 union brackets Fig 36 Teethbending Fig 37 Panelsassembly Fig 38 Coatingfixing Lift and bend...

Страница 20: ...with insulating material if it passes through a cold wall The outlet must be protected by a grid with wide mesh and a minimum total surface area of 40 cm2 If the pipes used are longer than 6 mt the ai...

Страница 21: ...rietyofUPSonthemarketregardingsizeandconstructionqualities wecannotguaranteeoperation once the stove is connected to these devices 6 13 CONNECTION TO THE EXTERNAL THERMOSTAT Fig 45 Graphicdisplay The...

Страница 22: ...ician in compliance with local regulations with the instructions of the manufacturer and those of your insurance company If there are no local regulations and no instruction from your insurance compan...

Страница 23: ...oval Fig 52 Bearingremoval Remove the spiral see Fig 51 If worn remove the bearing see Fig 52 and replace it To reassemble proceed in reverse order 7 3 FUME FAN CLEANING Clean every the year the fume...

Страница 24: ...on panel see Fig 57 Fig 58 Cleaningwithabrush Fig 59 Fumechambercleaning Clean the 2 internal fume passages with a brush see Fig 58 Clean with a vacuum cleaner the ash which has accumulated on the inn...

Страница 25: ...nAuthorizedTechnician Remove the left panel and clean with a vacuum cleaner the ash and the dust which has accumulated on the inner 7 8 FUME PIPES ANNUAL CLEANING Clean annually from soot with brushes...

Страница 26: ...Open fire door or open pellet door Close fire door and pellet door and check that there are no pellet grains at the gasket level Clogged stove Fume chamber cleaning Auger blocked by a foreign object...

Страница 27: ...ts Replace the gaskets Not sealed fume pipes Contact an expert stove repairer who will immediately provide for sealing the junctions with high temperature silicone and or for replacing pipes with thos...

Страница 28: ...ing or replacemente of the auger it is necessary to unscrew the three bolt of the geared motor and to extract it un screw the two screws lying under the geared motor vedi Fig 62 of the auger remove th...

Страница 29: ...at 13 O2 Min Max 9 9 16 5 mg Nm3 9 9 16 5 mg Nm3 9 9 16 5 mg Nm3 FLUE NEGATIVE PRESSURE Max 10 Pa 10 Pa 10 Pa ON SHARED FLUE NO NO NO FLUE GAS EXHAUST DIAMETER 80 mm 80 mm 80 mm FUEL Pellet 6 7 mm Pe...

Страница 30: ...age DUST CONTENT at 13 O2 Min Max 9 9 16 5 mg Nm3 FLUE NEGATIVE PRESSURE Max 10 Pa ON SHARED FLUE NO FLUE GAS EXHAUST DIAMETER 80 mm FUEL Pellet 6 7 mm PELLET HEATING CAPACITY 5 kWh kg PELLET HUMIDITY...

Страница 31: ...CADEL srl 31025 S Lucia di Piave TV Via Foresto sud 7 Italy Tel 39 0438 738669 Fax 39 0438 73343 www cadelsrl com www free point it Rev 00 2022...

Отзывы: