Page 15
8
Common Problems and Solutions
Note:
1. The inverter may respond according to the alarms uploaded by the battery.
2. When something might endanger the battery system happens, the battery system will take appropriate
protective measures, such as disconnecting the charge-discharge relays or opening the system switch; if the
battery system automatically opens the system switch, please contact our Technical Support.
(The alarms generated by the battery system can be uploaded to the inverter, or be viewed on the webpage
of battery system.)
8.1 Alarms Uploaded to the Inverter
No.
Alarm Name
Causes of Alarm
Solutions
1
Warning-Battery High
Voltage
The cell voltage is too high.
Normal alarm, no further action
required
2
Alarm-Battery High Voltage
The cell voltage is too high.
Normal alarm, no further action
required
3
Warning-Battery Low
Voltage
The cell voltage is too low.
Normal alarm, no further action
required
4
Alarm-Battery Low Voltage
The cell voltage is too low.
Normal alarm, no further action
required
5
Warning-Battery Low Temp
The cell temperature is too
low.
Normal alarm, no further action
required
6
Alarm-Battery Low Temp
The cell temperature is too
low.
Normal alarm, no further action
required
7
Warning-Battery High Temp
The cell temperature is too
high.
Normal alarm, no further action
required
8
Alarm-Battery High Temp
The cell temperature is too
high.
Normal alarm, no further action
required
9
Warning-Battery High
Current Discharge
The discharge current is too
high.
Normal alarm, no further action
required
10
Alarm-Battery High Current
Discharge
The discharge current is too
high.
Normal alarm, no further action
required
11
Warning-Battery High
Current Charge
The charge current is too high.
Normal alarm, no further action
required
12
Alarm-Battery High Current
Charge
The charge current is too high.
Normal alarm, no further action
required
13
Warning-BMS internal
Communication error
Normal alarm, no further action
required
14
Alarm-BMS internal
Internal fault of battery system.
Contact the Technical Support.
15
Alarm-Precharge fault
Internal fault of battery system.
Contact the Technical Support.