a. Normally, the charge limited current is determined by the ambient temperature
No.
Temperature
Current
1
Less than -10
℃
0
2
-10
℃
~0
℃
0.2C
3
0
℃
~10
℃
0.5C
4
10
℃
~50
℃
0.8C
5
Greater than 50
℃
0
b. Normally, the discharge limited current is determined by the ambient temperature
No.
Temperature
Current
1
Less than -20
℃
0
2
-20~40
℃
2C; if the actual discharge current is greater than 1.2C over 5min,
the discharge limited current will be renewed to 1C. 2 hours later, it
will be recovered to 2C discharge limited current.
3
40~50
℃
0.5C
4
Greater than 50
℃
0