X. Domestic Hot Water Piping
Install the domestic hot water piping as shown in Figure 10.1. Combi connections are ¾” NPT male thread. The components in
this system, and their functions are as follows:
1. ASSE 1070 or ASSE 1017 Listed Tempering Valve (Required) – This boiler is equipped with a control system that
attempts to regulate the DHW outlet temperature to a DHW set point (default set point is 120F – see Section XIII
for more information). As with all water heaters there are inherent limitations on the ability of the control system to
accurately regulate water temperature to this set point under all conditions. Extremely low draw rates and transitions from
heating to DHW are two examples of conditions that can cause the temperature of water leaving the boiler to significantly
exceed the DHW set point. To minimize “spikes” in DHW temperature, a tempering valve is therefore required. Select
and install in accordance with the valve manufacturer’s instructions and applicable codes. Note that some codes require
additional tempering devices at some of the fixtures as well.
2. Flow Restrictor (Optional) - If domestic hot water is drawn from at a rate in excess of the rating in Table 2.2, the
temperature of the hot water may be too low to be of use. The use of a flow restrictor will help prevent this problem by
limiting the rate at which water can pass through the DHW heat exchanger. If a restrictor is used, select one having a
rating in GPM approximately equal to that shown in Table 2.2 at the desired temperature rise.
3. Pressure Relief Valve (Required) - Limits the pressure in the domestic hot water piping. Use a valve designed for DHW
service, such as the Watts #3L or #53L. Note that this is a pressure relief valve, not a T&P valve. Select a valve with
a pressure setting less than or equal to 145 psi. Pipe the discharge to a safe location using piping the same size as the
discharge connection on the valve.
4. Hose Bib Valves
(Recommended) - These valves permit the DHW plate heat exchanger be periodically “back flushed” to
remove sediment.
5. Globe or Ball Valve
(Recommended) - Used to aid in back flushing the heat exchanger and to isolate the DHW piping if
it must be serviced. In addition, the upstream valve may be used to limit the DHW flow if necessary.
6. Thermal Expansion Tank
(Required if a backflow preventer is installed) – If a back flow preventer or check valve is
installed upstream of the cold connection, a thermal expansion tank will prevent the build-up of pressure in the DHW
piping. Use a thermal expansion tank designed for use in potable water service.
7. Unions – Improve serviceability of DHW piping.
DANGER - SCALD HAZARD
Under certain conditions this boiler can deliver domestic hot water (DHW) at temperatures in excess
of the DHW set point on the boiler control. An installer-supplied, ASSE 1017 or ASSE 1070 certified
tempering valve is therefore REQUIRED as part of this boiler’s installation.
• Select and install tempering valve in accordance with the valve manufacturer’s instructions and
applicable local codes. In the absence of such codes follow the Uniform Plumbing Code (IAPMO/UPC-
1). Also note that additional tempering valves may be required at the fixtures themselves.
NOTICE
• DHW feature on this boiler is designed to only to heat potable water (i.e. water from a well or water
utility that is suitable for drinking) having the following characteristics:
a) Hardness less than 200PPM
b) PH between 6 and 8
c) Chloride level less than 80PPM.
Use of water not having these characteristics could result in premature failure of the DHW handling
components in this boiler.
• Internal components near the Hot and Cold connections can be damaged by excessive heat during
soldering. If copper adaptors are mounted directly on the combi, solder adjacent piping to these
adaptors before installing them on the boiler. Failure to do so may cause internal leaks and/or other
damage to the boiler.
Содержание K2WTC
Страница 10: ...10 107774 01 9 17 Figure 4 1 Minimum Clearances To Combustible Construction IV Locating the Boiler continued ...
Страница 12: ...12 107774 01 9 17 Figure 5 1 Wall Layout Mounting Hole Location V Mounting The Boiler continued ...
Страница 81: ...81 107774 01 9 17 X Domestic Hot Water Piping continued Figure 10 1 Domestic Hot Water Piping ...
Страница 88: ...88 107774 01 9 17 XI Wiring continued XI Wiring continued ...
Страница 89: ...89 107774 01 9 17 Figure 11 7 Internal Wiring Connections Diagram XI Wiring continued ...
Страница 100: ...100 107774 01 9 17 Lighting and Operating Instructions XII Start Up and Checkout continued ...
Страница 141: ...141 107774 01 9 17 XVI Repair Parts continued ...
Страница 144: ...144 107774 01 9 17 XVI Repair Parts continued ...
Страница 147: ...147 107774 01 9 17 XVI Repair Parts continued ...
Страница 149: ...149 107774 01 9 17 XVI Repair Parts continued ...
Страница 151: ...151 107774 01 9 17 XVI Repair Parts continued 120 121 122 123 124 125 126 127 ...
Страница 158: ...158 107774 01 9 17 SERVICE RECORD DATE SERVICE PERFORMED ...
Страница 159: ...159 107774 01 9 17 SERVICE RECORD DATE SERVICE PERFORMED ...
Страница 160: ...160 107774 01 9 17 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...