44
107774-01 - 9/17
VII. Venting
E. Assembly of CPVC/PVC Vent Systems (continued)
WARNING
Asphyxiation Hazard. Failure to follow these instructions could cause products of combustion to
enter the building, resulting in severe property damage, personal injury or death.
Use all CPVC vent components for near-boiler vent piping before transitioning to Schedule 40 PVC
pipe (ASTM 2665) components for remainder of vent system.
Use CPVC vent components within any interior space where air cannot circulate freely, including
through vertical or horizontal chase ways, inside a stud wall, in closets and through wall penetrations.
The use of cellular core PVC (ASTM F891), cellular core CPVC or Radel (polyphenolsulfone is
prohibited.
All condensate that forms in the vent must be able to drain back to the boiler.
Never leave the boiler in operation without the gas sample cap in place (Figure 7.27).
E. Assembly of CPVC/PVC Vent Systems
1. Assemble the vent system, starting at the boiler:
a. If 3” PVC is to be used for venting, a 3” CPVC elbow and the 30” straight section of CPVC must be used before
transitioning to PVC. If necessary the 30” straight section of CPVC may be cut at any location and a CPVC elbow can be
inserted between the two resulting segments.
b. When cutting CPVC or PVC pipe, use a miter saw or a saw designed to cut PVC pipe. Use a miter box or other method to
cut pipe squarely. De-burr both the inside and outside of the cut end.
c. Dry fit all vent components before assembly.
d. The vent adaptor has three different inside diameters. The larger (upper) inside diameter accepts 3” CPVC pipe and is
used in this application (the middle inside diameter accepts 3” nominal PolyPro, Polyflue or InnoFlue, and the smaller,
lower inside diameter accepts 3” stainless steel). A locking band clamp in the adaptor prevents the vent pipe from coming
out of the adaptor once it is installed and tightened. Lubricate the upper gasket in the vent adaptor with water and insert
the first piece of 3” CPVC into the vent adaptor until it bottoms out. Tighten locking band clamp to secure vent pipe.
e. Assemble a 3” CPVC elbow and remainder of 30” CPVC piping before transitioning to PVC. If 3” PVC is used, the first
piece of PVC will either be connected to the CPVC elbow or the end of a section of CPVC vent pipe. In the latter case, a
PVC coupling may be used to connect the first piece of PVC to the last piece of CPVC.
f. Clean all CPVC and PVC components with the appropriate primer before cementing. Cement the vent system together,
starting at the boiler and following the instructions provided on the cans of cement and primer. Use a field supplied
cement and primer that is listed for use with the materials being joined (CPVC and/or PVC). The following, or its
equivalent, may be used to join CPVC to PVC:
• IPS Corporation #P-70 Primer
• IPS Corporation #790 Multi-Purpose Solvent Cement
Always use primer on both the pipe and fitting before applying the cement. Assemble the pipe in accordance with the
instructions on the cans of primer and cement.
g. Assemble the rest of the vent system, being sure to pitch horizontal sections back towards the boiler 1/4”/ft. Support the
vent at intervals not exceeding 4ft.
h. Maintain the clearances from the vent pipe outlined in Section VII - A of this manual. If exiting the exterior wall using
PVC pipe, use half of an appropriately sized wall thimble (or a sheet metal plate) on the exterior of the building, to
provide a weather tight seal while maintaining the proper clearance in the wall penetration. Seal the joint between the
pipe and the wall plate using RTV applied on the exterior side of the wall. This sealant must not restrain the expansion of
the vent pipe.
2. Installation of Air Intake System - Start assembly of the PVC air intake system at the boiler. Assembly of the air intake
system is done in the same manner as the vent system except as follows:
a. Drill a 7/32” clearance hole into the front side of the air intake adapter. Insert the first piece of PVC air intake pipe
into the air intake connection and drill a 1/8” tap hole into the PVC which lines up with the 7/32” clearance hole and
secure them together with a #10 x 1” sheet metal screw. Seal the joint between the intake pipe and the adaptor with
RTV.
b. All intake piping may be PVC.
c. There is a 0” minimum clearance between the air intake piping and all types of construction.
d. To the extent possible, pitch horizontal air intake piping towards the outdoors.
Содержание K2WTC
Страница 10: ...10 107774 01 9 17 Figure 4 1 Minimum Clearances To Combustible Construction IV Locating the Boiler continued ...
Страница 12: ...12 107774 01 9 17 Figure 5 1 Wall Layout Mounting Hole Location V Mounting The Boiler continued ...
Страница 81: ...81 107774 01 9 17 X Domestic Hot Water Piping continued Figure 10 1 Domestic Hot Water Piping ...
Страница 88: ...88 107774 01 9 17 XI Wiring continued XI Wiring continued ...
Страница 89: ...89 107774 01 9 17 Figure 11 7 Internal Wiring Connections Diagram XI Wiring continued ...
Страница 100: ...100 107774 01 9 17 Lighting and Operating Instructions XII Start Up and Checkout continued ...
Страница 141: ...141 107774 01 9 17 XVI Repair Parts continued ...
Страница 144: ...144 107774 01 9 17 XVI Repair Parts continued ...
Страница 147: ...147 107774 01 9 17 XVI Repair Parts continued ...
Страница 149: ...149 107774 01 9 17 XVI Repair Parts continued ...
Страница 151: ...151 107774 01 9 17 XVI Repair Parts continued 120 121 122 123 124 125 126 127 ...
Страница 158: ...158 107774 01 9 17 SERVICE RECORD DATE SERVICE PERFORMED ...
Страница 159: ...159 107774 01 9 17 SERVICE RECORD DATE SERVICE PERFORMED ...
Страница 160: ...160 107774 01 9 17 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...