INTRODUCTION 

Thank you for choosing this burley product. All of our products carry a CE mark which is awarded by 
an independent test house (notified body) and shows the fires have been type tested to meet the 
essential  requirements  of  the  European  Gas  Appliance  Directive  and  the  appropriate  British 
Standards. 

This  is  a  highly  efficient  Flueless  Inset  Live  Fuel  Effect  Appliance.  The  burner  system  is  very  clean 
burning and a catalyst cleans the combustion products even further. 

A  thermostat  in  the  burner  control  system  adjusts  heat  output  to  maintain  a  room  temperature, 
which can easily be set by the user. The appliance is operated via a battery powered remote control 
system. There is also a separate control to adjust the flame effect as required. Please demonstrate 
its operation to the customer before leaving. 

An oxygen depletion sensing pilot light is also fitted and will sense any significant oxygen depletion 
in the room and shut the fire down safely.  

 
 

1.

 

APPLIANCE DATA 

Refer  to  the  appliance  data  badge  (affixed  behind  controls  door) 

ENSURE  THAT  THE  LOCAL 

CONDITIONS OF USE CORRESPOND TO THE INFORMATION ON THE DATA BADGE.

 

 

 

 

Natural Gas G20 

 

LPG (Propane) G31 

Category 

 

I2H 

 

 

 

I3P 

Supply Pressure 

 

20mBar 

 

 

37mBar 

Inlet Pressure  

 

20mBar* 

 

 

37mBar* 

Burner Pressure 

(High)

  9.4mBar 

 

 

35.5mBar 

 

(Low)

 

2.2mBar 

 

 

8mBar   

Heat Input (Net) 

(High)

  3.5kW  

 

 

3.5kW    (250g/h) 

 

(Low)

 

1.7kW  

 

 

1.7kW    (120g/h) 

Inlet Connection 

 

8mm Compression   

8mm Compression 

Injector 

 

stereo 185 

 

 

stereo 95 

 

*

The inlet pressure must be 

/- 1mBar

 of specification with 

all

 gas appliances in the house 

switched on 

and also

 with just the Burley heater operating. If outside of this tolerance the fault is 

most likely to be in the installation pipe work or service governor at the meter. If the problem is the 
meter  governor,  this  is  the  property  of  the  gas  service  provider  (such  as  Transco  /  National  Grid 
0800  111999  or  Bord  Gais)  and  they  should  be  called  to  rectify  this.  The  fire  will  not  operate 
correctly if the pressures are incorrect. 

 

2.

 

UNPACKING THE APPLIANCE 

2.1

 

Carefully  examine  the  carton  for  damage  before  unpacking.  If  it  is  obviously  damaged, 
consult the supplier as to whether to proceed with the installation. 

2.2

 

Make sure the carton is stood upright and open the top. Remove the cardboard top fitting 
and place to one side; this box can be used as a hearth protector when installing the fire. 

2.3

 

Remove the fittings boxes contained within and open them and check the condition of the 
contents. Remove the fire and examine its general condition, paying particular attention to 
the frame, the glass front and fire box flanges. 

2.4

 

If  satisfied  by  the  general  condition,  place  the  decorative  components  to  one  side  and 
proceed  with  the  installation.  If  in  any  doubt,  seek  advice  from  the  supplier. 

Read  these 

instructions fully before proceeding even if you have fitted this model before. 

Содержание G4121 mk2

Страница 1: ...THE USER Burley Appliances Ltd Lands End Way Oakham Rutland LE15 6RB Telephone 44 0 1572 756956 Fax 44 0 1572 724390 e mail info burley co uk web www burley co uk G4121InstUser G20 31 Issue JAN08 v 1...

Страница 2: ...t High 3 5kW 3 5kW 250g h Low 1 7kW 1 7kW 120g h Inlet Connection 8mm Compression 8mm Compression Injector stereo 185 stereo 95 The inlet pressure must be within 1mBar of specification with all gas ap...

Страница 3: ...cubic feet by 35 3 Adjoining spaces not separated by a door may be combined 3 7 The heater must not be used on or against a combustible surface 3 8 No furniture soft furnishings decorations wall cove...

Страница 4: ...t for servicing 4 5 The surfaces of the appliance become very hot during use 4 6 Before cleaning or maintenance switch fire OFF and allow to cool 4 7 Any purpose provided ventilation should be checked...

Страница 5: ...etc All gas work should be undertaken by a competent person see General Requirements 8 Siting the Appliance 8 1 If the appliance is to be in or in front of an open fireplace the chimney or flue MUST b...

Страница 6: ...rner and the front log is pushed to the extreme left hand side as shown Take the 2 loose logs and position them as shown onto the cut outs on the base log taking care to locate them correctly to ensur...

Страница 7: ...f it does not light repeat the operation a few times Continue to hold knob for 15 20 sec s to establish the pilot and then release If pilot fails to establish turn off wait 1 minute then repeat lighti...

Страница 8: ...Protective clothing is not required but normal hygiene rules of no smoking eating or drinking in the work area should be followed Controls The system for monitoring the oxygen supply to the burner is...

Страница 9: ...IN THE UNIQUE POSITION OF KNOWING THAT EVERY APPLIANCE LEAVES THE FACTORY IN PERFECT WORKING ORDER Due to our policy of continual improvement and development the exact accuracy of descriptions and il...

Страница 10: ...956 Do not use any other type of paint GENERAL REQUIREMENTS 1 The heater is intended as a secondary heat source Check that a primary source of heat such as radiators is present in the room If insuffic...

Страница 11: ...e the fire purely as a heater in which case they will select a flame height then set the thermostat to a comfort level In both cases if the room gets too hot the thermostat will reduce the fire to pil...

Страница 12: ...obstructed TURN OFF PROCEDURE To extinguish the pilot turn the valve to the OFF position Note that if the gas supply fails at any time the pilot will extinguish Leave for one minute then carry out the...

Отзывы: