26
pH sensor - parameter
3.
Configure and activate the error limits of the pH value.
→
Go to device
pH sensor MS01
function
pH sensor
tab
Parameter
.
→
Select
Error triggers
.
→
Select
Low pH
and enter a pH value, under which an error event is generated. Validate with
.
→
Select
High pH
and enter a pH value, above which an error event is generated. Validate with
.
→
Select
Activation flags
. Select
Low pH
and
High pH
. Validate with
.
When the pH value is less than the set limit, an error event is generated. Details about the error event are
given in chpt.
When the pH value is more than the set limit, an error event is generated. Details about the error event
are given in chpt.
→
To enable the monitoring, i.e. to be informed when the pH value is outside the normal range, enable the
diagnostics. See chpt.
10.5
Monitor the temperature value of the water sample
Do the following procedure:
1. Make sure that the login user level is
Installer
. Refer to chpt.
2.
Configure and activate the warning limits of the temperature value.
→
Go to device
pH sensor MS01
function
pH sensor
tab
Parameter
.
→
Select
Warning triggers
.
→
Select
Low temperature
and enter a temperature value, under which a warning event is generated.
Validate with
.
→
Select
High temperature
and enter a temperature value, above which a warning event is generated.
Validate with
.
→
Select
Activation flags
. Select
Low temperature
and
High temperature
. Validate with
.
When the temperature value is less than the set limit, a warning event is generated. Details about the
warning event are given in chpt.
19.3.11.
When the temperature value is more than the set limit, a warning event is generated. Details about the
warning event are given in chpt.
3.
Configure and activate the error limits of the temperature value.
→
Go to device
pH sensor MS01
function
pH sensor
tab
Parameter
.
→
Select
Error triggers
.
→
Select
Low temperature
and enter a temperature value, under which an error event is generated. Val
-
idate with
.
English
Type MS01