Type 8756 BATCH
Electrical connection
27
M12 thread is internally connected to FE
1
2
3
4
5
6
Fig. 11: BüS /CANopen: Pin assignment, 5-pin M12 male connector (A coding)
1 Shield
2 24 V
3 GND
4 CAN_H
5 CAN_L
6 Coding lug
Take a strand of the cable shielding and insert the strand into pin 1.
Screw the mating female connector to the 5-pin male connector, to the torque given by the manufac-
turer of the mating female connector.
Do the functional earthing of the product.
Connect the functional earth [
6.4
Connect the functional earth
To do the functional earthing of the product, obey the following instructions:
Use a green-and-yellow cable that is as short as possible. And the cable cross-section must be at least
equal to the cross section of the power-supply cable.
With a flat screwdriver of size 6.5 mm, loosen the M4 screw.
M4 screw
Fig. 12: Location of the M4 screw for the connection of the functional earth
Attach the green-and-yellow cable to the M4 screw with a cable lug.
Tighten the M4 screw to a torque of 1,8 N·m...2 N·m, that is 1,33 lbf·ft...1,47 lbf·ft.