Anti-Vibration Supports
5
8
We reserve the right to make any changes due to technical modifications!
Boiler Installation and Maintenance Manual SB735 • Issue 10/2003
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
5
Anti-Vibration Supports
z
Anti-vibration supports are standard equipment on
the SB735/1200 model; they can be ordered
separately for the other models.
z
Insert the longer part of the longitudinal anti-vibration
bracket (Fig. 3,
Item.
4) from the front and the
shorter part (Fig. 3,
Item.
3) from the rear into the
channel sections (Fig. 3,
Item.
2).
z
Position both rails of the anti-vibration boiler support,
in accordance with dimensions shown in Table 4, on
the floor where the boiler is to be installed.
J
NOTICE!
Prepare the foundation, where the anti-vibration
supports are to be located, with a smooth trowel
of ±1/8“ per linear foot and with a slight rise to
the back. This ensures an even load distribution
over the longitudinal anti-vibration brackets,
and adequate boiler ventilation.
z
Position, align and place the boiler on the supports.
The boiler support should be flush with the boiler
back wall. The end-stop plates (Fig. 3,
Item.
1)
should contact the channel section of the boiler.
Fig. 3
Anti-vibration support
Item. 1:
End-stop plates
Item. 2:
Channel section
Item. 3:
Short anti-vibration bracket
Item. 4:
Long anti-vibration bracket
Table. 4 Support dimensions
1)
Standard delivery
2)
Accessories
Boiler
Type
Boiler-
Model
Length
F
[Inch]
Distance
C
[Inch]
1200
1)
90
46
SB735
970
2)
90
43
¾
790
2)
73
½
44
F
C
2
4
3
1