Initial burner start-up
6
Buderus Blue Flame Burner BE 1.3 - 2.3 - Specifications subject to change without notice.
21
6.7.4 Measuring CO content (carbon monoxide)
The CO content (carbon monoxide content) must be
less than 50 ppm (CO < 50 ppm).
z
In case of deviations from the specified value: Detect
and correct fault (see Chapter 10 „Troubleshooting
burner failures“, page 39).
6.7.5 Measuring chimney draft
If the chimney draft is excessive, a barometric damper
must be installed.
6.7.6 Run particle test
The particle count must be 0 (SMOKE = 0).
z
In case of deviations from the specified value: correct
fault (see Chapter 10 „Troubleshooting burner fail-
ures“, page 39).
NOTICE
If an excessive CO value is measured on
initial start-up, gas generated from organic
matter (e.g. burner door insulation) may be
the reason.
z
Therefore, run the burner for at least 20
- 30 minutes before measuring the CO
content.
CAUTION!
SYSTEM DAMAGE
from clogged vent pipe.
The installation must be performed by a
qualified installer in accordance with regu-
lations put forth in NFPA-31 Installation of
Oil-Burning Equipment.
The installation must comply with all local
and national codes, regulations and au-
thorities having jurisdiction regarding the
installation of oil fired boilers.