Technical data and scope of delivery
4
Buderus Blue Flame Burner BE 1.3 - 2.3 - Specifications subject to change without notice.
10
4.2
Burner tubes
4.3
Settings and nozzle specification
Atmospheric combustion
Fig. 5
Dimensions of burner tube
Stamp
Burner Logatop
Stamp
Tube
n x
4
A *
in inch
n x
4
B *
in inch
LA
in inch
LB
in inch
BE 1.3 - 21
63028636
D83/L224/4,3/2,6
12 x 0.17
6 x 0.1
0.71
3
BE 2.3 - 28
63028637
D83/L224/5,9/4,8
12 x 0.17
6 x 0.1
0.71
3
BE 2.3 - 34
63028638
D83/L224/7,0/5,7
12 x 0.17
6 x 0.1
0.71
3
Table 3 Ceramic burner tubes and their dimensions
* Tolerances of all measurements are -1/16“
NOTICE
Specification is based on an intake air tem-
perature of 68 °F and an installation below
1650 ft. elevation (see Chapter 6.7.2 „Mea-
suring CO
2
-value“, page 19).
Settings, nozzle installation
1
G125 BE atmospheric combustion
Burner type
BE 1.3 – 21
BE 2.3 – 28
BE 2.3 – 34
Output
MBtu/h
72
96
116
Mixing system
1.1 – 21
1.1 – 28
2.1 – 34
Nozzle
1
Danfoss
0.45 gph
80° HFD
Danfoss
0.55 gph
60° HFD
Danfoss
0.65 gph
80° HFD
Oil pressure
psi
189 – 290
218 – 334
218 – 334
Oil
gph
0.58
0.76
0.95
Air intake setting (estimated)
4.5
5.5
5.5
Static air pressure
W. C.
[inch
H
2
O]
3.8 – 4.4
3.8 – 4.4
3.8 – 4.5
Combustion chamber pressure
0 – 0.15
0 – 0.16
0 – 0.24
Min draft (required draft)
2
0
0
0
Available draft
0.12
0.12
0.12
CO
2
-without hose connected
%
13.0 – 13.5
13.0 – 13.5
13.0 – 13.5
CO
2
-with hose connected
%
13.5 – 14.0
13.5 – 14.0
13.5 – 14.0
CO-Value
ppm
< 50
< 50
< 50
Table 4 Settings and nozzle installation for G125 BE with atmospheric combustion
1
Recommended: use only the nozzle types specified here.
2
In chimney systems with negative pressure.
Содержание Logatop BE 1.3
Страница 53: ...Notizen Buderus Blue Flame Burner BE 1 3 2 3 Specifications subject to change without notice 53 ...
Страница 54: ...Notizen Buderus Blue Flame Burner BE 1 3 2 3 Specifications subject to change without notice 54 ...
Страница 55: ...Notizen Buderus Blue Flame Burner BE 1 3 2 3 Specifications subject to change without notice 55 ...