10
Troubleshooting
Logano plus GB402 - Subject to technical modifications!
63
B
7A
550
Undervoltage. The mains voltage
is too low.
The power supply must not
fall below 195 V.
Ensure the correct
power supply.
B
7A
551
Voltage
interruption.
There has been a
brief power failure.
Check the power cable for
possible loose contacts.
Check the wiring and
correct contacts of the
mains plug at the MC10 or
SAFe.
Remedy any contact
problems.
B
7P
549
The safety
chain has
opened.
The continuity of
the external
components tied
into the MC10
safety chain has
been interrupted.
Check the continuity of the
components.
If required, replace faulty
components.
B
8L
534
No gas
pressure or
additional flue
gas pressure
limiter
(pressure
> 7.5 bar) has
responded.
There is no gas
pressure although
solenoid valve 1
should have
opened. The
burner makes three
successive
attempts at
starting, then there
is a delay of one
hour, before
making three more
start attempts.
Check that the gas tap is
open.
Replace the gas valve if
required.
Check whether there is gas
pressure.
Check the gas pressure.
Check whether the flue gas
pressure limiter has
responded.
Reset the flue gas
pressure limiter.
Check the flue for
blockages.
Check electrode.
Replace electrode if
required.
Check ignition transformer. Replace ignition
transformer if required.
Check gas filter for
contamination.
Replace gas filter if
required.
V
8P
580
Solenoid valve
1 leaking.
The valve test
system has
detected an
unacceptably high
leakage rate on
solenoid valve 1.
Check gas valve for
contamination.
Gas filter fitted.
Replace gas valve.
V
8U
581
Solenoid valve
2 leaking.
The valve test
system has
detected an
unacceptably high
leakage rate on
solenoid valve 2.
Check gas valve for
contamination.
Gas filter fitted.
Replace gas valve.
Type
1)
Display
code
Fault
code
Cause
Description
Test procedure/cause
Action
Tab. 21 Fault displays
1) V = interlocking; B = blocking