6
Installation
Logano plus GB402 - Subject to technical modifications!
19
6.2
Installing the condensate hose
B
Remove the cap from the filler hole in the siphon
supplied and fill with approx. 2 litres of water.
B
Fit elbow [4] with inserted gasket onto the filler hole.
B
Fit the condensate hose from flue system [3] with a
hose clip to the elbow.
B
Fit the siphon to the outlet on condensate tray [2].
B
Install neutralising systems (accessories) in
accordance with the installation instructions, either
inside the boiler or on site.
B
Connect the condensate hose from the siphon with a
slope to the neutralising system.
B
Connect the condensate hose from the boiler flue
connection with a slope to the neutralising system.
Fig. 10 Installing the condensate hose
1
Neutralising system (accessory)
2
Condensate tray
3
Condensate hose connection to the flue gas system
4
Elbow, filler hole
5
Siphon outlet to neutralising system or drain line
6
Siphon
B
Make the connection to the sewerage system in
accordance with the instructions of the neutralising
system and locally applicable regulations.
Information regarding the condensate hose.
B
Carefully drain the condensate created
inside the boiler and flue (route the flue
with a slope towards the boiler).
B
Drain the condensate into the public
sewerage system in accordance with the
requirements in your country.
B
Observe regional regulations.
DANGER:
Risk to life through poisoning!
Open connections or siphons not filled with
water can cause a risk to life from escaping
flue gas.
B
Fill the siphon with water.
Neutralising systems are available as
accessories and can be fitted inside the
boiler casing.
Where the neutralising system is installed
outside the boiler, there is the option of
guiding the condensate hose through the
aperture in the back panel.