12
Boiler size
Natural gas H (G20)
Natural gas L (DE)
Natural gas L (G25) (NL)
Wobbe index 14.9 kWh/m
3
Wobbe index 12.8 kWh/m
3
Wobbe index 12.2 kWh/m
3
Gas throughput
Gas throughput
Gas throughput
[m
3
/h]
[m
3
/h]
[m
3
/h]
320 -5
32.3
34.3
37.6
395 -6
39.8
42.4
46.4
470 -7
47.4
50.4
55.2
545 -8
55.0
58.4
64.0
620 -9
62.5
66.5
72.8
Tab. 4
Gas throughput (relative to 15 °C gas temperature and 1013 mbar air pressure)
Country
Boiler
size
Mains supply
pressure
P [mbar]
Gas
category
Gas type already set on the
boiler, or corresponding gas
type conversion kits supplied
Delivered set to the
mains supply pressure
in mbar
1)
DE
320-620
20
I
2ELL
G20/G25
20
AT, CH, SK
320-620
20
I
2H
G20
20
ES, GB, IE, IT,
PT, SI
320-620
20
I
2H
G20
20
EE, DK, HR,
NO, SE
320-620
20
I
2H
G20
20
FR
320-620
20/25
I
2ESi
G20
20
BE
320-620
20/25
I
2E(R)B
G20
20
CZ
320-620
20
I
2H
G20
20
LU
320-620
20
I
2E
G20
20
NL
320-620
25
I
2L
G25
25
PL
320
20
I
2E
G20
20
PL
395-620
20
I
2ELw
G20
20
HU
320
25
I
2H
G20
25
HU
395-620
25
I
2HS
G20
25
BA, BG, GR
320-620
20/50
II
2H3B/P
G25
25
BY, CN, RO,
RU, UA
320-620
20/50
II
2H3P
G25
25
Tab. 5
Country-specific gas categories and supply pressures
1) The gas supply utility must guarantee the minimum and maximum pressures (acc. to national regulations for public gas supply).