Technical Information Logamatic LON-Gateway - Subject to modifications resulting from technical improvements!
9
Product description
2
y
= Basic equipment
o
= Optional (required accessories in parentheses)
–
= Not required
Requirement
1 boiler
5 heating zones
1 DHW
1 solar
2 boiler
5 heating zones
1 DHW
1 solar
4 boilers
1 heating zone
1 DHW
Expansion
for heating
zones 3, 4
1)
1) Logamatic 4122 required if LON heating zones 3 and 4 are required in one and two-boiler systems.
Logamatic
4211
Logamatic
4121
Logamatic
4321
Logamatic
4323
Logamatic
4122
Boiler with
Logamatic 4000
y
(ZM422)
–
o
2)
(FM458)
2) Function module FM458 combines boiler with the Logamatic 4000 and Logamatic EMS control system.
o
2)
(FM458)
–
Boiler with
Logamatic EMS
–
y
(ZM424)
o
(FM456 in
slot 2)
o
2)
(FM458)
o
2)
(FM458)
–
DHW heating
y
(ZM422)
y
(ZM424)
o
(FM441 in slot 2)
o
(FM441 in slot 1)
–
LON HK 1
o
(FM442 in
slot 1)
y
(ZM424)
o
(FM442 in
slot 1)
o
(FM441 in
slot 1)
o
(FM441 in slot 1)
–
LON HK 2
o
(FM442 in
slot 1)
y
(ZM424)
o
(FM442 in
slot 1)
–
–
–
LON HK 5
y
(ZM422)
–
–
o
(FM442 in
slot 3)
–
–
–
Solar DHW
heating
o
(FM443 in
slot 2)
o
(FM443 in slot 2)
o
(FM443 in
slot 2)
–
–
–
LON HK 3
LON HK 4
o
1)
o
1)
o
1)
o
(4322 with
FM442 in
slot 2)
–
–
o
(FM442 in
slot 2)
LON flasher
version
LON Flasher
2B_00
LON Flasher
2B_E_00
LON Flasher
2B_E_00
LON Flasher
2B_00
LON Flasher
4B_00
LON Flasher
4B_00
XIF file version
LON_2B_00
LON_2B_00 LON_2B_00 LON_2B_00 LON_4B_00 LON_4B_00
Address of
Logamatic
control panel
1
1
1
1
3)
3) ECOCAN-BUS address of the Logamatic 4321 control panel on the first boiler; additional boilers with
Logamatic 4321 control panel of the 4322 are assigned ECOCAN-BUS addresses 2 to 4.
1
3)
1
2
Tab. 5
Overview of LON-Gateway and Logamatic control system