Network interface
Technical Information Logamatic LON-Gateway - Subject to modifications resulting from technical improvements!
32
3
3.4.4 Strategy
In the "Strategy" section, the values for the entire heating system are summarized. This is especially
important for multi-boiler systems (cascades).
Format:
Changing the operating mode
With the HVAC_heat / HVAC_off setting, the operating mode for the consumer is changed
externally via the LON data bus.
Set range: 32 °F to 194 °F (0 °C to 90 °C); in 1-degree intervals
Note:
230 °F (110 °C) is an invalid value (e.g. no temperature sensor connected, sensor defective, etc.).
Note:
230 °F (110 °C) is an invalid value (e.g. no temperature sensor connected, sensor defective, etc.).
23
Operating mode (D/N/A) system
SNVT_hvac_mode
(108)
nviAnl_TgNtAt
2
Tab. 70 Value for changing the operating mode of the entire system (all heating zones)
Value
Designation
Description
0
HVAC_AUTO
The system works according to the internal setting on the control panel
(automatic mode).
1
HVAC_heat
The system is turned on (all on) and works in manual day mode.
6
HVAC_off
The system is turned off (all off).
Tab. 71
24
System supply set point
temperature
SNVT_temp_p(105)
nviAnlVorgabe_Tp
2
Tab. 72 Value for changing the system set point temperature (boiler supply temperature)
25
System supply set point
temperature
SNVT_temp_p(105)
nvoAnlVLIst_Tp
2
Tab. 73 Display of the currently-valid set point temperature for the boiler system
26
System supply actual
temperature
SNVT_temp_p(105)
nvoAnlRLIst_Tp
2
Tab. 74 Display of the currently-measured supply temperature for the boiler system