Network interface
Technical Information Logamatic LON-Gateway - Subject to modifications resulting from technical improvements!
14
3
3.2
Description of the SNVTs for variant 2 boilers
Note:
The right column indicates the number of bytes.
3.2.1 General
Format: YYYY/MM/DD hh:mm:ss
Note:
230 °F (110 °C) is an invalid value (e.g. no temperature sensor connected, sensor defective, etc.)
For the error list, see Chapter 7, page 43.
Error messages are displayed as 2-byte values (2 x 8 bits). The first byte (the first 8 bits seen from
the left) is the interpretation of the error message of control panel address 2. The second byte (the
remaining 8 bits) is the interpretation of the error message of control panel address 1:
Errors are displayed as binary values and must be converted to decimal values. By comparing with
the error list (see Chapter 7, page 43), the associated texts are assigned to the error numbers.
Example: see page 27
0
Time
SNVT_time_ stamp(84)
nviUhrzeit
7
Tab. 8
Value for comparison of the time in the Buderus control system with the LON network
1
Outdoor temperature
SNVT_temp_p(105)
nvoAussen_Tp
2
Tab. 9
Display of the current outdoor temperature
2
Error message 1 control
panel address 1 + 2
SNVT_state(83)
nvoFehler1
2
Tab. 10 Output for error messages: error 1 of control panel 1 and 2
First byte - error boiler 2
Second byte - error boiler 1
Display
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Interpretation
2
0
2
1
2
2
2
3
2
4
2
5
2
6
2
7
2
0
2
1
2
2
2
3
2
4
2
5
2
6
2
7
Tab. 11