Technical Information Logamatic LON-Gateway - Subject to modifications resulting from technical improvements!
25
Network interface
3
Boiler 3
45
Status burner boiler 3
SNVT_lev_cont (21)
nvoKS3_BrStatus
46
Temperature boiler 3 (FK) actual
SNVT_temp_p(105)
nvoKS3VLIst_Tp
47
Boiler hours of operation 4000 boiler 3 level 1
SNVT_time_hour(124)
nvoKS3Br4000S1_h
48
Boiler hours of operation 4000 boiler 3 level 2
SNVT_time_hour(124)
nvoKS3Br4000S2_h
49
Pump 4000 boiler 3
SNVT_lev_cont (21)
nvoKS3PU_4000
50
Burner hours of operation EMS boiler 3
SNVT_time_hour(124)
nvoKS3Br_EMS_h
51
Pump EMS boiler 3
SNVT_lev_cont (21)
nvoKS3PU_EMS
Boiler 4
52
Status burner boiler 4
SNVT_lev_cont (21)
nvoKS4_BrStatus
53
Temperature boiler 4 (FK) actual
SNVT_temp_p(105)
nvoKS4VLIst_Tp
54
Boiler hours of operation 4000 boiler 4 level 1
SNVT_time_hour(124)
nvoKS4Br4000S1_h
55
Boiler hours of operation 4000 boiler 4 level 2
SNVT_time_hour(124)
nvoKS4Br4000S2_h
56
Pump 4000 boiler 4
SNVT_lev_cont (21)
nvoKS4PU_4000
57
Burner hours of operation EMS boiler 4
SNVT_time_hour(124)
nvoKS4BrEMS_h
58
Pump EMS boiler 4
SNVT_lev_cont (21)
nvoKS4PU_EMS
Status
59
Status ECOCAN-BUS
SNVT_state(83)
nvo_CAN_Adressen
60
Status LON version
SNVT_str_asc (36)
nvo_LONVersion
No. Meaning
SNVT type
SNVT name
Tab. 45 Service menu navigator