Technical Information Logamatic LON-Gateway - Subject to modifications resulting from technical improvements!
17
Network interface
3
Notes:
• The room set point night temperature specifies the temperature level in the setback mode or night
mode for the consumer. With this setting, the heating curve moves in parallel. If you change the
room set point temperature by 2 °F (1 °C), then the supply temperature changes by approx.
6 °F (3 °C).
• The room set point night temperature is not active with the setback type "off."
• The room set point night temperature is not taken into account with the setting heating system
"constant." The temperature set in the control panel for the heating zone and the temperature
setback are active.
Setting: 52 °F to 86 °F (11 °C to 30 °C) in 1-degree intervals
Notes:
• The room set point day temperature specifies the temperature level in day mode for the
consumer. With this setting, the heating curve moves in parallel. If you change the room set point
temperature by 2 °F (1 °C), then the supply temperature changes by approx. 6 °F (3 °C).
• The room set point day temperature is not active with the setback type "off."
• The room set point night temperature is not taken into account with the setting heating system
"constant." The temperature set in the control panel for the heating zone and the temperature
setback are active.
Note:
230 °F (110 °C) is an invalid value (e.g. no temperature sensor connected, sensor defective, etc.).
8
Room set point day
temperature
SNVT_temp_p(105)
nviHK1RaumSTg_Tp
2
Tab. 16 Value for changing the set point temperature for the setback heating mode (day mode)
9
Room set point temperature
SNVT_temp_p(105)
nviHK1Raum_S_Tp
2
Tab. 17 Display of the currently-valid room set point temperature for the consumer
10
Operating mode (Day/Night/
Auto)
SNVT_hvac_mode
(108)
nvoHK1Betrieb
1
Tab. 18 Display of the currently-valid operating mode for the consumer
11
Heating zone supply actual
temperature
SNVT_temp_p(105)
nvoHK1VLIst_Tp
2
Tab. 19 Display of the currently-measured supply temperature for the consumer