XT-Micro Control Panel
22
OUTSIDE AIR CONTROL:
CAT
Cooling Air Timer. The CAT timer comes into play when the system terminates Cooling and
goes into Standby mode. The default setting is three minutes. The CAT timer will start timing as
soon as the system switches to Standby. This is a countdown timer, and once it reaches 0, the
system will determine if the outside air temperature is below the start temperature. The system
will go back into the Cooling mode if cooling is available. The CAT timer has an override condi-
tion - when the outside air is .3° less than the start temperature, the CAT will not be in affect.
RAS
Plenum Rise Above Setpoint. The default setting for the RAS is .3°. This is used to determine
when cooling air is no longer available. If the plenum temperature is higher than the RAS setting
and the outside air temp is higher than the start temperature, the system will terminate cooling.
Summary of Cooling Air Logic:
Cooling air available
If OSA < Start_T and CAT satisfied or if (OSA - 3) < Start_T.
Cooling air not available
If OSA > Start_T
Terminate Cooling Run
If OSA > Start_T and Plenum temp > RAS and MCR satisfied.
The FORCE COOLING can be used to force the system into a cooling mode. The time clock must be set to al-
low cooling. Once the system is in cooling, it will run for the minimum cooling time.
The FORCE REFRIG can be used to force the system into a refrigeration mode. The time clock must be set to
allow refrigeration. Once the system is in refrigeration, it will run for the minimum refrigeration time.