XT-Micro Control Panel
19
Timed / Purge:
The system is in Timed and the time purge cycle is active. At the
designated time, the fresh air door will open to the max door setting
and purge for the programmed time. This cycle has been triggered by
time and not the CO2 sensor.
Cooling / CO2:
The system is in Cooling and the CO
2
level is above The CO2 setpoint.
The return air heaters are active to help open the doors and purge the
CO
2
.
Refrig / CO2:
The system is in Refrigeration and the CO
2
level is above CO2 setpoint.
The fresh air doors are being used to purge the CO
2
.
Heat:
This mode is used to turn on return air heaters when the system is
running in Cooling, the doors are closed and the plenum temperature
has drop below the Setpoint minus the heat differential.