XT-Micro Control Panel
11
(Programmable Parameter)
Ref Sp (Refrigeration Setpoint %) Ref Sp is the speed in percent that the fans will run
when the system is in the Refrigeration mode. Ref Sp is a programmable parameter.
Press ENTER to change.
Purge Sp is the speed in percent that the fans will run when the system is in a Purge.
This is a programmable parameter. Press Enter and then use the right arrow to get the
cursor in the lower line.
Ref Sp 75.0*
Purge Sp 100*
Heat Diff 0.5*
AxH Temp 50*
AxH Time 10*
(Programmable Parameter)
Heat Diff (Heat Differential) The Heat Diff is used when the plenum temperature drops
below the temperature Setpoint. If the plenum is less than SP - Heat Diff then the return
air heater will turn on. This is a programmable parameter and can be changed by press-
ing ENTER. This value is a positive number.
(Programmable Parameter)
AxH Temp (auxiliary heat) The AxH Temp is a setpoint of aux heat. The heat could be
located any where in the storage and would be connect to the Aux output. The Aux 1
config byte needs to be set to 5 for this to work. If the outside air temperature drops be-
low the AxH Temp setting the Aux 1 output would turn on.
This has an associated timer AxH Time. The outside air needs to be below the AxH
Temp for the amount of time programmed. The AxH Temp can be programmed by
pressing the ENTER. Press the right arrow to move the cursor to the AxH Time.