XT-Micro Control Panel
16
Program Miscellaneous: This allows access to a number of miscellaneous parameters.
Press the right key to access.
Program
Miscellaneous
Cell Eff 90*
RAS 3*
Refrig Switch
Auto *
Cavity Switch
Auto *
Door Switch
Auto *
(Programmable Parameter)
Cell Eff (Evaporative Cooling Efficiency) The efficiency of different evaporative cooling
cells can vary greatly depending on a number of variables. Cell Eff allows you to set the
efficiency of a given evaporative cooling system. This can be determined by setting the
cell to 100 percent and watching in on a good warm dry day. The setting is from 0 to 100
percent.
RAS (Rise Above Setpoint) This value is what terminates the Cooling air available sig-
nal. The RAS is in 1/10 of a degree. A setting of 3 would be .3 degrees above setpoint.
If the Plenum temperature gets above the RAS setting and the outside air is above the
Start temperature then the Cooling mode will be terminated. Press the ENTER key to
change the RAS parameter.
Refrig Switch (Refrigeration Switch) The switch has three positions, Off, Manual and
Auto. Off will prevent the refrigeration from starting. Manual position will all the desired
output percentage to be entered. Used the up and down arrows to change the percent-
age. When done testing make sure to go back to Auto or Off. The Auto position will al-
low the controller to turn the refrigeration on and off. Press ENTER to change the posi-
tion.
Cavity Switch: The switch has three positions, Off, Manual and Auto. This switch con-
trols the output for the cavity heater. Off, Manual and Auto. Off will prevent the cavity
heat from turning on. Manual will turn the cavity heat on all the time. Auto will allow the
program to turn the cavity heat on and off.
Door Switch: The door switch has three positions. This enables the doors to be shut off
or controlled in manual or auto. In manual the doors can be opened or closed using the
up and down keys. Pres the ENTER button to change the mode. If in manual, remem-
ber when done testing to switch back to auto.
AOM Switches
Auto-Off-Manual Switches. These are software switches that can be changed remotely.
For these switches to work the actual hardware switch on the board needs to be in the
Auto position.
Fan Switch
Auto *
Programmable Parameter)
The Fan Switch has three modes. Off, Manual and Auto. In off the Fans will not run re-
gardless of the Stop / Start switch position. In Manual the Fans will run when ever the
Stop / Start switch is in the Start position. In auto the controller will turn the fans on and
off as long as the Stop / Start switch is in the Start position.