KTF/100HPS Operation
KTF/100HPS
- 3-9 -
P1 Programming Level
LFA m/min
#
ADVANCED
#
MENU P1
The P1 programming level allows you to setup 4 parameters:
1)
Device main tension;
2)
Tolerance with respect to the main tension;
3)
Max deviation time from tolerance band;
4)
Increment/Decrement resolution of graduated tension.
With the KTF/100HPS in
CONTROL
status,
(LFA nnnn displayed on LCD)
press
and hold it down for 3 seconds.
The display will show the
ADVANCED
label and the KTF/100HPS will switch to
PROGRAM status.
or
to continue.
to start programming of parameters belonging to P1 menu.
P1.1
MAIN TENSION
Tension value with which the KTF device must operate to create the desired article
(INC/DEC active).
[Allowed values 0.2 ÷ 100.0 grams].
During programming phase you cannot set a tension value lower than the
ERROR
TENSION
value or greater than the difference between the device full scale value
(100.0 g.)
and the
ERROR TENSION
value.
Choose the desired value using:
(to increase the value)
or
(to decrease the value).
to confirm.
P1.2
ERROR TENSION
Tolerance band beyond which the machine will be stopped. The error indication
and machine stop occur only if such tolerance is exceeded for the time period set in
the next parameter
(
TIME ALARM
).
[Allowed values ± 0.1 ÷ 99.5 grams (with automatic limitation to 0.4 grams for
what concerns the negative tolerance)].
Choose the desired value using:
(to increase the value)
or
(to decrease the value).
to confirm.