4.1 - Starting the transmitter
M2007/3en
TCT-2301 Operating instructions
45
©BTG 2004
4.1.3
Select measuring unit
Unit selection is made using
,
. Press
to
switch between mg/l and %. End by pressing
.
4.1.4
Setting measuring span
Try to keep the measuring span as narrow as possible.
Specify the consistency values represented by output signals of 4 mA and
20 mA respectively.
Confi-
gure
Tx.
Spec
Unit
xxx
Send
page
Tag: 25NT1237 Range x
---------------
0% 53.3% 100%
Cons. 1.30%
TCT-2301
4-20mA MODEMPRINTER
PWR
EJECT
ON/OFF
MEMORY CARD
SPC-1000
Communication Terminal
Read
data
Edit
Range
x
Confi-
gure
Cali-
brate
4 mA
1.00%
20 mA
3.00%
Damp
1s
Offset
0.00%
Misc.
Note !
Trend
Calib-
ration
curve
Send
data
4 mA
1.00%
Tag: 25NT1237 Range 1
---------------
0% 53.3% 100%
Cons. 1.30%
TCT-2301
20 mA
3.00%