Outputs
The three relay outputs can be configured as follows:
1. Output type 1 (COMMS):
•
BSIA 175 Mode – operates when either path is in fault but in conjunction with Pin 11
ATS allows the panel to interrogate the device to determine a single or dual path
fault (default).
•
Single path fault – operates when either path is in fault.
•
Dual path fault – operates when both paths are in fault.
•
Mobile 1 path fault – operates when the Mobile 1 Path is in fault.
2. Output type 2 (FUNC):
•
Dual path fault – operates when both paths are in fault (default).
•
User – allow the relay to be operated remotely via the app or portal (default).
•
Mobile 2 path fault – operates when the mobile path 2 is in fault.
•
RPS – return path signal operates in conjunction with Pin 4.
•
Fire NAK – Fire pin not acknowledged. Operates in conjunction with Pin 1.
•
Keyswitch – allows panel to be set/unset via the BT Redcare customer app.
3. Output type 3 (FIRE):
•
User – allows the relay to be operated remotely via the app or portal.
•
Fire ACK – Fire pin acknowledged. Operates in conjunction with Pin 1 (default).
•
Keyswitch – allows panel to be set/unset via the BT Redcare customer app.
Keyswitch mode:
•
Momentary – allow the FUNC relay, when set to Keyswitch, to be operated remotely
via the app or portal by one pulse of the relay (default).
•
Latched – allow the FUNC relay, when set to Keyswitch, to be operated remotely
via the app or portal by latching the relay.
18