6.5 

e.g. for 150mm dia. damper, and 12.5mm wall board, cut hole should be 195mm (150+(2x10)+(2x12.5))  

6.6 

Mark out position and size of required cut size on the wall. 

6.7 

Using appropriate means, cut the hole in the wall and line opening by adding track and batons (fig 1). 

6.8 

Check opening size is correct. 

6.9 

Position damper centrally in opening and fix Installation Plate to wall using drywall screws of sufficient 
length to engage with track. 

6.10 

ALL Ø5mm fixing holes, except the 4off unused corner fixings must be used. 

6.11 

Install from ONE side. There is no need to fill void or add pattress on non -access side. 

6.12 

Test unit - (refer to sections 10). 

6.13 

Complete Installation check list. 

(sec’n 14). 

 

 

7.  Block wall and Floor Installation Procedure (refer to figure 3)

 

 

 
 

7.1 

  Finished aperture size can be square or circular and 0 to 20mm larger     

          than the nominal damper diameter. This leaves 10mm nominal gap all 
          round. For core made apertures, please be aware of the rivet tails on the 
          back of the installation plate. A shallow provision to be made as 
          appropriate. 

7.2 

Preferably, prepare aperture whilst building wall/floor, or cut aperture if 
wall/floor already exists. 

7.3 

Cut size = finished size. 

7.4 

E.g. for 250 dia. damper, cut hole should be 270mm square  or circular 
(250+20) 

7.5 

Mark out the position and size of the required aperture on the wall/floor. 

7.6 

Using appropriate means, cut the aperture in the wall/floor. 

7.7 

Position damper centrally in wall/floor aperture depth. Fix Installation Plate 
to wall or top face of floor. 

7.8 

There are a variety of proprietary fixings available. Fixings must be fire rated (stee l, NOT aluminum or 
plastic). Check minimum dimension specification between fixing and edge of  aperture. BSB recommend 
steel anchor type bolts Ø5mm minimum). 

7.9 

There is a pair of fixing holes at each of the installation plate corners, but only one fixing is r equired per 
corner. On larger dampers, there are also mid-span fixing holes that must be used. ALL Ø5mm fixing holes, 
except the 4 off unused corner fixings must be used. 

7.10 

Test Unit. (see section 11) 

7.11 

Complete Installation check list. (sec’n 14). 

 

Figure 3 

Содержание FD-C

Страница 1: ...e the structure is sufficiently supported to conform to design specification 3 4 Dry wall openings must be lined Please see figure 1 3 5 Ensure that appropriate fire rated plasterboard is used through...

Страница 2: ...Control Officer and or specifying authority 5 10 The installation method contained herein assumes the wall has been built prior to the damper opening preparation Optionally the opening may already be...

Страница 3: ...vet tails on the back of the installation plate A shallow provision to be made as appropriate 7 2 Preferably prepare aperture whilst building wall floor or cut aperture if wall floor already exists 7...

Страница 4: ...e to produce an interference fit The installation plate face and all edges should be glued in place and a bead of intumescent mastic applied at all joints 8 1 4 Note two layers of 50mm min thickness a...

Страница 5: ...he as tested installation method 8 2 7 Screw in 50mm long spiral pig tail fixings through installation plate into batt material utilising one of the pair of corner holes and all intermediate fixing ho...

Страница 6: ...hen required 9 3 The cleats can be easily bent out at right angles by hand using a medium size flat head screwdriver at one of the cleats pressed out corners to start see figure 7 9 4 The cleats can b...

Страница 7: ...dertaken annually Local regulations conditions may override this with periodic Inspection being carried out more frequently where corrosive or dirty conditions prevail The maintenance log should be re...

Страница 8: ...l pliable Damper not in expected normal state Fusible link FL missing Fit Fusible Link FL Part No 201448 Fusible link FL not tightened properly Tighten Fusible Link FL Fusible Link FL has activated Me...

Страница 9: ...LL OPEN FINAL INSPECTION BY Print name Signature Company Date This document is available for free download from the BSB website This document is subject to change without notice BSB Engineering Servic...

Отзывы: