background image

VIII.

ENSURE ADEQUATE OUTDOOR-AIR SUPPLY

Outdoor air is pulled from underneath the home, passed across the
outdoor-air coil, then pushed out through the roof cap exhaust.
Since the outdoor-air is pulled from beneath the home, it is very
important that the amount of ventilation panels or vents is
adequate. The underpinning vent panels or foundation vents are
rated for the amount of air that passes through them in sq in. of net
free area. Ensure that you have the correct amount of ventilation
needed for unit being installed. (See Table 8.)

IX.

CONSTRUCT

OUTDOOR-AIR

TUNNEL

(IF

RE-

QUIRED)

NOTE:

This is an OPTIONAL installation procedure to alleviate

problems that may occur with your air conditioner or heat pump
unit and various other appliances or ambient conditions.

A.

Determine if an Outdoor-Air Tunnel is Required

We recommend that this procedure be used for any one or a
combination of the following conditions:

1. A fireplace is installed and gets its fresh air from underneath

structure.

Indication to use: When conditioner or heat pump turns on,
smoke from fireplace backdrafts and enters structure.

2. A gas water heater is installed that uses fresh air from

underneath structure.

Indication to use: When your air conditioner or heat pump
turns on, the pilot light for the water heater is blown out.

3. In extremely cold regions where water pipes may freeze.

Indication to use: In winter, pipes freeze.

B.

Build Outdoor-Air Tunnel

NOTE:

The equipment and materials to install this duct work are

NOT factory supplied, nor is manufacturer responsible for deter-
mining if this procedure should be utilized.

If it is determined that an outdoor-air tunnel is required, locate unit
air intake which comes through bottom board of home and build
outdoor-air tunnel as follows:

1. Using pressure-treated 2 X 2’s or similar material, frame a

tunnel from skirting or foundation wall to entrance of
outdoor-air plenum. (See Fig. 27 for a typical air tunnel.)

2. The condensate drain must not be allowed to drain inside air

tunnel. Pipe to outside of home. (See. Fig. 28.)

CAUTION:

The tunnel and grille or screen must meet

the minimum requirements listed in Table 8 to get the
proper airflow to the unit intake. Failure to adhere to this
caution will affect the unit’s capacity and efficiency
ratings. A larger net free area may be used.

3. Attach 1-in. duct board to frame built in item 1.

4. Seal all joints thoroughly with caulking and/or duct tape.

5. Set base of walls about 2 in. in ground and backfill around

to provide a good air seal. (See Fig. 28.)

6. Install a louver or a screen over opening of air tunnel where

it penetrates skirting or foundation of home.

X.

REFRIGERANT

The unit is pre-charged at the factory to the correct operating
charge and should not require adjustment. However, should an
adjustment be required or if the unit requires service, adhere to the
following precautions.

WARNING:

Gage ports are equipped with Schrader

valves. To prevent personal injury, wear safety glasses
and gloves when handling refrigerant.

CAUTION:

Compressor damage may occur if system is

overcharged.

WARNING:

Do not vent refrigerant to atmosphere.

Recover all refrigerant before system repair or final unit
disposal to avoid personal injury or death. Use all service
ports and open all flow-control devices, including sole-
noid valves.

CARE AND MAINTENANCE

For continuing high performance, and to minimize equipment
failure, it is essential that periodic maintenance be performed on
this equipment. Consult your servicing contractor or User’s
Manual for the proper frequency of maintenance. Frequency of
maintenance may vary depending on geographic areas, such as
coastal application.

Leave User’s Manual with homeowner.

Explain system operation and maintenance procedures outlined in
User’s Manual.

TABLE 8—VENTILATION REQUIREMENTS

UNIT SIZE

MINIMUM NET FREE OPEN AREA (SQ. IN.)

018

400

024

450

030

675

036

700

—13—

Содержание MA1A

Страница 1: ...manufactured homes These units are available in the cooling sizes shown in Table 1 The MA1A and MH1A are single package units All components including outdoor coil compressor and refrigerant tubing a...

Страница 2: ...e thermostat wire with less than the recommended number of conductors CAUTION Failure to adhere to indoor air outdoor air and exhaust air requirements as listed in the following sections will void uni...

Страница 3: ...clearance C Recommended Unit Clearances For serviceability and elimination of compressor vibration trans mission it is recommended that the sides and back of unit be installed with a minimum 1 in clea...

Страница 4: ...n See Fig 9 4 Place base template assembly over hole and mark indoor air plenum cutout in supply duct trunk measuring 13 in by 9 1 8 in See Fig 10 Mark condensate drain hose and outdoor air plenum cut...

Страница 5: ...nit and base template into floor Tighten screws flush to foam seal Overtightening screws will tip unit forward on foam seal Do NOT use any other procedure to permanently secure unit to structure 4 Cov...

Страница 6: ...panel or fuse box Refer to Table 3 and Table 4 for required circuits and recommended wire size for each circuit The unit is equipped with circuit breakers enclosed in wiring compartment This compartme...

Страница 7: ...ps Ampacity Wire Size Max Fuse Size Amps Max Wire Length Ft Amps Ampacity Wire Size Max Fuse Size Amps Max Wire Length Ft 5 018 024 030 036 23 9 29 9 10 30 80 N A N A N A N A N A 10 018 024 030 036 44...

Страница 8: ...LE TYPE APPLICATION THERMOSTAT NO OF CONDUCTORS REQUIRED 18 GAGE REQUIRED CONNECTIONS WIRING DIAGRAM Air Conditioner Robertshaw TX400 42K 4 G R Y W Fig 18 TSTATPPNAC01 A 5 R C W W1 Y Y2 G Fig 19 TSTAT...

Страница 9: ...s 4 Drill two 3 16 in mounting holes in wall where marked 5 Secure mounting base to wall with 2 screws and anchors provided making sure all wires extend through mounting base 6 Adjust wire length and...

Страница 10: ...3 Push all but approximately 2 in of thermostat cable back into wall Seal opening around cable to prevent drafts through hole which could interfere with operation of unit Fig 19 Air Conditioning Circu...

Страница 11: ...e to wall with 2 screws and anchors provided making sure all wires extend through mounting base 7 Adjust wire length and routing to allow proper closure of thermostat Strip each wire end no more than...

Страница 12: ...be adjusted NOTE Refer to Installation Instructions packaged with thermo stat for additional information D Make Low Voltage Connections at Unit Attach thermostat wires to low voltage terminal block on...

Страница 13: ...from skirting or foundation wall to entrance of outdoor air plenum See Fig 27 for a typical air tunnel 2 The condensate drain must not be allowed to drain inside air tunnel Pipe to outside of home See...

Страница 14: ...UCTBOARD 2 X 2 TREATED LUMBER Fig 28 Drain Pipe Routing A95384 NET FREE AREA SEE VENTILATION REQUIREMENTS TABLE SIZES MAY VARY AS LONG AS THE MINIMUM NET FREE OPEN AREA INCLUDING GRILLE MEETS THE REQU...

Страница 15: ...FSET FLASHING FLASHING ROOFCAP ATTIC AREA ATTIC AREA FLEX DUCT FLEX DUCT NOTE THE FLEX DUCT SHOULD BE A STRAIGHT RUN FROM UNIT TO ROOFCAP TYPICAL FRONT VIEW TYPICAL SIDE VIEW TYPICAL FRONT VIEW TYPICA...

Страница 16: ...The compressor should energize and cool air should blow through registers Once cooling test is complete return system control to OFF setting Wait 5 minutes c Set system control to HEAT and raise tempe...

Отзывы: