Bryant MA1A Скачать руководство пользователя страница 5

NOTE:

Do not let indoor-air collar extend down into duct. It

MUST be flush with top of duct trunk. If collar does not fit
properly, minor adjustments may have to be made to collar.

8. Use Flex-Mend or equivalent RTV caulk to seal bottom

board to outdoor-air plenum.

WARNING:

Non-foil-type tapes will not withstand the

temperature of heated air from unit and may be a fire
hazard. Failure to tape joint will allow heated or cooled
air to leak beneath home. A failure to follow this warning
could result in a fire or explosion, and personal injury or
death.

V.

INSTALL UNIT

A.

Setting Unit

CAUTION:

Do not move unit on an unprotected floor.

Damage to floor will result.

1. If necessary, use an appliance dolly to position unit into

enclosure, being careful not to disturb foam seal on tem-
plate. When unit’s front edge is in line with front edge of
base template, set unit upright onto base template. (See Fig.
11.)

CAUTION:

Only minor movement is allowed when

aligning holes in unit base with holes in template to
prevent damage to foam air seal.

2. Remove front grille of unit (if necessary) as shown in Fig.

12 and make minor adjustments in location of unit if
necessary to align screw holes in bottom rail of unit with
screw holes in base template.

3. The unit should be secured permanently to structure by

driving 2 wood screws through mating holes in bottom rail
of unit and base template into floor. Tighten screws flush to
foam seal. Overtightening screws will tip unit forward on
foam seal. Do NOT use any other procedure to permanently
secure unit to structure.

4. Cover unit top as shown in Fig. 12. Cut a hole with a

diameter of approximately 15 in. through ceiling and roof
directly over outdoor-air exhaust. If hole in roof and ceiling
cannot be aligned directly over each other, a small bend in
the flexible duct may be required. Acceptable misalignment
of hole in ceiling and transition is a maximum of 2 in. per
each 12 in. of flex duct in elevation, up to a maximum of 6
in.

5. Seal any opening with mastic to prevent loss of conditioned

air into attic space.

B.

Exhaust Air Venting

1. Apply a generous amount of mastic to roof surface and

around hole cut for outdoor-air duct to pass through. (See
Fig. 13.) Lower duct down through hole in roof and ceiling
and fasten flashing to roof with screws.

2. Apply additional mastic or sealant around flashing perim-

eter base to provide protection against rainwater leaking
under flashing.

Fig. 11—Setting Unit on Base Template

A95347

NOTE:

TILT UNIT APPROXIMATELY 45° WHILE MOVING IT

INTO PLACE TO AVOID DISTORTION OF FOAM SEAL.

BASE TEMPLATE

Fig. 12—Securing Unit to Floor

A95348

WOOD SCREWS

NOTE: SCREW HOLES IN BOTTOM RAIL OF UNIT MUST 
ALIGN WITH HOLES IN METAL BASE TEMPLATE.

TEMPORARILY COVER HOLE
WHILE THE 15-IN. CUTOUT IN
THE CEILING AND ROOF
ARE BEING MADE

Fig. 13—Outdoor-Air Duct Installation

A95349

APPLY MASTIC TO
SEAL ROOF CAP
TO ROOF

15-IN. DIAMETER 
HOLE

ROOF

CEILING

—5—

Содержание MA1A

Страница 1: ...manufactured homes These units are available in the cooling sizes shown in Table 1 The MA1A and MH1A are single package units All components including outdoor coil compressor and refrigerant tubing a...

Страница 2: ...e thermostat wire with less than the recommended number of conductors CAUTION Failure to adhere to indoor air outdoor air and exhaust air requirements as listed in the following sections will void uni...

Страница 3: ...clearance C Recommended Unit Clearances For serviceability and elimination of compressor vibration trans mission it is recommended that the sides and back of unit be installed with a minimum 1 in clea...

Страница 4: ...n See Fig 9 4 Place base template assembly over hole and mark indoor air plenum cutout in supply duct trunk measuring 13 in by 9 1 8 in See Fig 10 Mark condensate drain hose and outdoor air plenum cut...

Страница 5: ...nit and base template into floor Tighten screws flush to foam seal Overtightening screws will tip unit forward on foam seal Do NOT use any other procedure to permanently secure unit to structure 4 Cov...

Страница 6: ...panel or fuse box Refer to Table 3 and Table 4 for required circuits and recommended wire size for each circuit The unit is equipped with circuit breakers enclosed in wiring compartment This compartme...

Страница 7: ...ps Ampacity Wire Size Max Fuse Size Amps Max Wire Length Ft Amps Ampacity Wire Size Max Fuse Size Amps Max Wire Length Ft 5 018 024 030 036 23 9 29 9 10 30 80 N A N A N A N A N A 10 018 024 030 036 44...

Страница 8: ...LE TYPE APPLICATION THERMOSTAT NO OF CONDUCTORS REQUIRED 18 GAGE REQUIRED CONNECTIONS WIRING DIAGRAM Air Conditioner Robertshaw TX400 42K 4 G R Y W Fig 18 TSTATPPNAC01 A 5 R C W W1 Y Y2 G Fig 19 TSTAT...

Страница 9: ...s 4 Drill two 3 16 in mounting holes in wall where marked 5 Secure mounting base to wall with 2 screws and anchors provided making sure all wires extend through mounting base 6 Adjust wire length and...

Страница 10: ...3 Push all but approximately 2 in of thermostat cable back into wall Seal opening around cable to prevent drafts through hole which could interfere with operation of unit Fig 19 Air Conditioning Circu...

Страница 11: ...e to wall with 2 screws and anchors provided making sure all wires extend through mounting base 7 Adjust wire length and routing to allow proper closure of thermostat Strip each wire end no more than...

Страница 12: ...be adjusted NOTE Refer to Installation Instructions packaged with thermo stat for additional information D Make Low Voltage Connections at Unit Attach thermostat wires to low voltage terminal block on...

Страница 13: ...from skirting or foundation wall to entrance of outdoor air plenum See Fig 27 for a typical air tunnel 2 The condensate drain must not be allowed to drain inside air tunnel Pipe to outside of home See...

Страница 14: ...UCTBOARD 2 X 2 TREATED LUMBER Fig 28 Drain Pipe Routing A95384 NET FREE AREA SEE VENTILATION REQUIREMENTS TABLE SIZES MAY VARY AS LONG AS THE MINIMUM NET FREE OPEN AREA INCLUDING GRILLE MEETS THE REQU...

Страница 15: ...FSET FLASHING FLASHING ROOFCAP ATTIC AREA ATTIC AREA FLEX DUCT FLEX DUCT NOTE THE FLEX DUCT SHOULD BE A STRAIGHT RUN FROM UNIT TO ROOFCAP TYPICAL FRONT VIEW TYPICAL SIDE VIEW TYPICAL FRONT VIEW TYPICA...

Страница 16: ...The compressor should energize and cool air should blow through registers Once cooling test is complete return system control to OFF setting Wait 5 minutes c Set system control to HEAT and raise tempe...

Отзывы: