background image

C.

Mount Wall Thermostat and Connect Thermostat

Wires

Determine the type of thermostat needed for unit application and
follow instructions in the appropriate section below.

ROBERTSHAW AIR CONDITIONING THERMOSTAT

1. Remove cover (friction fit) from thermostat body by grip-

ping at top and bottom and lifting from subbase. Use
extreme care not to damage working parts.

2. Remove subbase from thermostat body by loosening cap-

tive screws.

3. Hold subbase level against wall in final thermostat location.

Mark wall with a pencil where screws will attach subbase to
wall. Use designated subbase mounting holes only.

4. Set subbase aside and drill mounting holes in wall with

3/32-in. drill bit.

5. Route thermostat wires from hole in wall through opening

in center of subbase.

6. Attach thermostat subbase to wall using mounting screws

and predrilled holes in wall.

NOTE:

Make sure white wire on thermostat subbase is connected

to A2 terminal.

7. Strip approximately 1/2-in. of insulation off end of each

wire. Connect thermostat wires to appropriate thermostat
screw terminals on subbase. (See Fig. 18.)

8. Push excess wire back into wall. Seal hole in wall to prevent

drafts.

9. Mount thermostat body on subbase with captive screws.

10. Set heat anticipator indicator (located in upper left corner of

thermostat body) to appropriate value based on the heater
size for unit being installed. (See Table 6.)

11. Install thermostat cover. Carefully align "D" shaped dial

shaft with matching shaped hole in hub of setting dial, then
press cover carefully on thermostat body.

12. Set outdoor thermostat to 50°F.

NOTE:

Refer to Installation Instructions packaged with thermo-

stat for additional information.

ELECTRONIC

AIR

CONDITIONING

THERMOSTATS

(PROGRAMMABLE AND NON-PROGRAMMABLE)

1. Open thermostat rear door (mounting base) to expose

mounting holes. The base can be removed to simplify
mounting. Snap apart carefully at hinge to separate mount-
ing base from remainder of thermostat.

2. Route thermostat wires through large hole in mounting

base.

3. Level mounting base against wall and mark wall through 2

mounting holes.

4. Drill two 3/16-in. mounting holes in wall where marked.

5. Secure mounting base to wall with 2 screws and anchors

provided, making sure all wires extend through mounting
base.

6. Adjust wire length and routing to allow proper closure of

thermostat. Strip each wire end no more than 1/4-in. to
prevent adjacent wires from shorting together. Match and
connect equipment lead wire to correct terminals of the
thermostat connector. (See Fig. 19 and 20.)

NOTE:

All TSTAT models have no batteries and are not "power

stealing." They do require 24 vac (R and C terminals) to be
connected for proper operation. Thermostat will not operate
without these 2 connections.

7. Push excess wiring into wall. Seal hole in wall to prevent

drafts.

8. Snap hinge back together.

9. Turn on power to unit.

10. Reconfigure thermostat to energize fan (G) terminal

with call for heat (W).

Since this is a self-contained unit, there is no furnace or fan
coil to energize the blower when electric heat is initiated.
The thermostat MUST be reconfigured to start blower when
electric heat is selected (G is energized whenever W is
energized).

a. Non-Programmable Model

(1.) Enter thermostat configuration mode by pressing

and holding FAN button for approximately 10 sec.
The room temperature disappears and display
should read "1-." Thermostat is now in configura-
tion mode.
NOTE: If FAN button is pressed again or if no
button is pressed for 60 sec, thermostat will exit
configuration mode and return to normal operation.
To re-enter configuration mode, the FAN button
must be pressed and held for 10 sec again.

(2.) Use up and down buttons until thermostat display

reads "5-."

(3.) Press MODE button once to display current selec-

tion of ON or OFF. Factory default is OFF.

(4.) Use the up or down button to change from OFF to

ON.

(5.) Press FAN button to exit configuration mode.

NOTE:

Refer to electronic thermostat Installation Instructions for

more information if needed.

Fig. 18—Air Conditioner Circuit Connections

(Robertshaw Thermostat)

NOTE:

Connect only terminals shown to thermostat.

A95354

THERMOSTAT

CONTROL

VOLTAGE

TERMINAL

STRIP

FAN

24VAC HOT

COOL

HEAT

GREEN

RED

YELLOW

WHITE

G

R

Y

W

G

R

Y

W

TABLE 6—HEAT ANTICIPATOR VALUES FOR

AIR CONDITIONING UNITS

HEATER SIZE (KW)

ANTICIPATOR SETTING

0

N/A

5

0.16

10

0.16

15

0.32

20

0.32

N/A—Not Applicable

—9—

Содержание MA1A

Страница 1: ...manufactured homes These units are available in the cooling sizes shown in Table 1 The MA1A and MH1A are single package units All components including outdoor coil compressor and refrigerant tubing a...

Страница 2: ...e thermostat wire with less than the recommended number of conductors CAUTION Failure to adhere to indoor air outdoor air and exhaust air requirements as listed in the following sections will void uni...

Страница 3: ...clearance C Recommended Unit Clearances For serviceability and elimination of compressor vibration trans mission it is recommended that the sides and back of unit be installed with a minimum 1 in clea...

Страница 4: ...n See Fig 9 4 Place base template assembly over hole and mark indoor air plenum cutout in supply duct trunk measuring 13 in by 9 1 8 in See Fig 10 Mark condensate drain hose and outdoor air plenum cut...

Страница 5: ...nit and base template into floor Tighten screws flush to foam seal Overtightening screws will tip unit forward on foam seal Do NOT use any other procedure to permanently secure unit to structure 4 Cov...

Страница 6: ...panel or fuse box Refer to Table 3 and Table 4 for required circuits and recommended wire size for each circuit The unit is equipped with circuit breakers enclosed in wiring compartment This compartme...

Страница 7: ...ps Ampacity Wire Size Max Fuse Size Amps Max Wire Length Ft Amps Ampacity Wire Size Max Fuse Size Amps Max Wire Length Ft 5 018 024 030 036 23 9 29 9 10 30 80 N A N A N A N A N A 10 018 024 030 036 44...

Страница 8: ...LE TYPE APPLICATION THERMOSTAT NO OF CONDUCTORS REQUIRED 18 GAGE REQUIRED CONNECTIONS WIRING DIAGRAM Air Conditioner Robertshaw TX400 42K 4 G R Y W Fig 18 TSTATPPNAC01 A 5 R C W W1 Y Y2 G Fig 19 TSTAT...

Страница 9: ...s 4 Drill two 3 16 in mounting holes in wall where marked 5 Secure mounting base to wall with 2 screws and anchors provided making sure all wires extend through mounting base 6 Adjust wire length and...

Страница 10: ...3 Push all but approximately 2 in of thermostat cable back into wall Seal opening around cable to prevent drafts through hole which could interfere with operation of unit Fig 19 Air Conditioning Circu...

Страница 11: ...e to wall with 2 screws and anchors provided making sure all wires extend through mounting base 7 Adjust wire length and routing to allow proper closure of thermostat Strip each wire end no more than...

Страница 12: ...be adjusted NOTE Refer to Installation Instructions packaged with thermo stat for additional information D Make Low Voltage Connections at Unit Attach thermostat wires to low voltage terminal block on...

Страница 13: ...from skirting or foundation wall to entrance of outdoor air plenum See Fig 27 for a typical air tunnel 2 The condensate drain must not be allowed to drain inside air tunnel Pipe to outside of home See...

Страница 14: ...UCTBOARD 2 X 2 TREATED LUMBER Fig 28 Drain Pipe Routing A95384 NET FREE AREA SEE VENTILATION REQUIREMENTS TABLE SIZES MAY VARY AS LONG AS THE MINIMUM NET FREE OPEN AREA INCLUDING GRILLE MEETS THE REQU...

Страница 15: ...FSET FLASHING FLASHING ROOFCAP ATTIC AREA ATTIC AREA FLEX DUCT FLEX DUCT NOTE THE FLEX DUCT SHOULD BE A STRAIGHT RUN FROM UNIT TO ROOFCAP TYPICAL FRONT VIEW TYPICAL SIDE VIEW TYPICAL FRONT VIEW TYPICA...

Страница 16: ...The compressor should energize and cool air should blow through registers Once cooling test is complete return system control to OFF setting Wait 5 minutes c Set system control to HEAT and raise tempe...

Отзывы: