Bryant MA1A Скачать руководство пользователя страница 4

D.

Installation of Unit Behind a Louvered Door or

Enclosed in Closet

If unit is installed behind a louvered door and louvers are directly
in front of unit’s intake grille, a 2-in. clearance is recommended
between door and front of unit. If louvers are installed in upper part
of door so they are not directly in front of intake grill, a minimum
7-in. clearance is recommended between door and front of unit.
This also applies if a solid wall is used instead of a louvered door.
Should the louver be installed somewhere other than in front of
unit (for example, to the side of unit), consult your distributor
before proceeding to obtain recommended clearances. The recom-
mended minimum return-air requirements to be used are shown in
Table 2.

IV.

PREPARE FLOOR AND BASE

A.

Install Installation Kit

Installing installation kit requires a hole through floor of home
approximately 18-1/2 in. wide by 19-1/2 in. deep to provide access
from unit to supply duct trunk and outside air.

NOTE:

The diagrams show a typical installation. The actual

method of installation will be dictated by model and manufacturer
of the home. Installer will determine the best method to use.

1. Construct a boxed-in area of framework under unit location

slightly larger than the 18-1/2-in. by 19-1/2-in. hole to
provide adequate support for unit. (See Fig. 8.)

2. Locate supply duct trunk so that it runs under front edge of

hole. Back edge of supply duct trunk should be approxi-
mately 8 in. from back of hole. (See Fig. 9.)

3. After floor section is complete; locate, mark, and cut a hole

through floor approximately 18-1/2 in. by 19-1/2 in. (See
Fig. 9.)

4. Place base template assembly over hole and mark indoor-air

plenum cutout in supply duct trunk measuring 13 in. by
9-1/8 in. (See Fig. 10.) Mark condensate drain hose and
outdoor-air plenum cutouts in insulation and vapor barrier
or drain to outside.

CAUTION:

Be careful not to crimp drain hose attached

to condensate drain cup.

CAUTION:

Failure to route drain hose where it will not

be kinked will cause drain trap to overflow, leaking water
onto floor.

5. Remove base template assembly. Reach through hole and

cut holes through vapor barrier and insulation for outdoor-
air plenum and condensate drain hose to extend through or
drain to outside. Also cut 13-in. by 9-1/8-in. hole in duct
trunk. (See Fig. 10.)

6. Bend every other tab up 90 degrees on indoor-air collar as

shown in Fig. 10.

7. Insert base template assembly into supply duct and secure it

with 4 flat-head screws, 1 in each corner. Bend remaining
tabs up 90 degrees locking indoor-air collar securely to
supply duct trunk. Use mastic or foil-type duct tape to seal
any openings. (See Fig. 10.)

TABLE 2—MINIMUM RETURN-AIR REQUIREMENTS

UNIT SIZE

NET FREE OPEN AREA (SQ IN.)

018

300

024

375

030, 036

450

Fig. 8—Typical Framework Construction

A95343

 FLOOR JOIST

SUPPLY-AIR DUCT

181⁄2

″ 

191⁄2

″ 

Fig. 9—Dimensions of Hole

A95344

FRONT OF UNIT

18

1

2

″ 

19

1

2

″ 

2

″ 

TYP.

 

2

APPROX.

8

WALLS

FLOOR

FLOOR JOIST 
FRAMING

HOME DUCT TRUNK

Fig. 10—Installation of Base Template, Indoor-Air Collar,

and Outdoor-Air Plenum

A95345

13

″ 

9

1

8

″ 

FOAM AIR SEAL

FLAT-HEAD
WOOD SCREW

BASE
TEMPLATE

DRAIN CUP

INDOOR AIR 

COLLAR

OUTDOOR AIR 

PLENUM

BEND 

ALTERNATE 

TABS

DUCT TRUNK

DRAIN HOSE

(PIPE TO OUTSIDE 

OF STRUCTURE)

INDOOR AIR 

CUTOUT

13

″ 

x 9

1

8

NOTE: THE DRAIN CUP, FOAM AIR SEAL, OUTDOOR-AIR 
PLENUM, AND INDOOR-AIR COLLAR ARE PREASSEMBLED 
AT FACTORY.

DO NOT USE
FRONT INSIDE
HOLES

—4—

Содержание MA1A

Страница 1: ...manufactured homes These units are available in the cooling sizes shown in Table 1 The MA1A and MH1A are single package units All components including outdoor coil compressor and refrigerant tubing a...

Страница 2: ...e thermostat wire with less than the recommended number of conductors CAUTION Failure to adhere to indoor air outdoor air and exhaust air requirements as listed in the following sections will void uni...

Страница 3: ...clearance C Recommended Unit Clearances For serviceability and elimination of compressor vibration trans mission it is recommended that the sides and back of unit be installed with a minimum 1 in clea...

Страница 4: ...n See Fig 9 4 Place base template assembly over hole and mark indoor air plenum cutout in supply duct trunk measuring 13 in by 9 1 8 in See Fig 10 Mark condensate drain hose and outdoor air plenum cut...

Страница 5: ...nit and base template into floor Tighten screws flush to foam seal Overtightening screws will tip unit forward on foam seal Do NOT use any other procedure to permanently secure unit to structure 4 Cov...

Страница 6: ...panel or fuse box Refer to Table 3 and Table 4 for required circuits and recommended wire size for each circuit The unit is equipped with circuit breakers enclosed in wiring compartment This compartme...

Страница 7: ...ps Ampacity Wire Size Max Fuse Size Amps Max Wire Length Ft Amps Ampacity Wire Size Max Fuse Size Amps Max Wire Length Ft 5 018 024 030 036 23 9 29 9 10 30 80 N A N A N A N A N A 10 018 024 030 036 44...

Страница 8: ...LE TYPE APPLICATION THERMOSTAT NO OF CONDUCTORS REQUIRED 18 GAGE REQUIRED CONNECTIONS WIRING DIAGRAM Air Conditioner Robertshaw TX400 42K 4 G R Y W Fig 18 TSTATPPNAC01 A 5 R C W W1 Y Y2 G Fig 19 TSTAT...

Страница 9: ...s 4 Drill two 3 16 in mounting holes in wall where marked 5 Secure mounting base to wall with 2 screws and anchors provided making sure all wires extend through mounting base 6 Adjust wire length and...

Страница 10: ...3 Push all but approximately 2 in of thermostat cable back into wall Seal opening around cable to prevent drafts through hole which could interfere with operation of unit Fig 19 Air Conditioning Circu...

Страница 11: ...e to wall with 2 screws and anchors provided making sure all wires extend through mounting base 7 Adjust wire length and routing to allow proper closure of thermostat Strip each wire end no more than...

Страница 12: ...be adjusted NOTE Refer to Installation Instructions packaged with thermo stat for additional information D Make Low Voltage Connections at Unit Attach thermostat wires to low voltage terminal block on...

Страница 13: ...from skirting or foundation wall to entrance of outdoor air plenum See Fig 27 for a typical air tunnel 2 The condensate drain must not be allowed to drain inside air tunnel Pipe to outside of home See...

Страница 14: ...UCTBOARD 2 X 2 TREATED LUMBER Fig 28 Drain Pipe Routing A95384 NET FREE AREA SEE VENTILATION REQUIREMENTS TABLE SIZES MAY VARY AS LONG AS THE MINIMUM NET FREE OPEN AREA INCLUDING GRILLE MEETS THE REQU...

Страница 15: ...FSET FLASHING FLASHING ROOFCAP ATTIC AREA ATTIC AREA FLEX DUCT FLEX DUCT NOTE THE FLEX DUCT SHOULD BE A STRAIGHT RUN FROM UNIT TO ROOFCAP TYPICAL FRONT VIEW TYPICAL SIDE VIEW TYPICAL FRONT VIEW TYPICA...

Страница 16: ...The compressor should energize and cool air should blow through registers Once cooling test is complete return system control to OFF setting Wait 5 minutes c Set system control to HEAT and raise tempe...

Отзывы: