3. Disconnect wires from existing thermostat, 1 at a time. Be

careful not to allow wires to fall back into wall.

4. As each wire is disconnected, record wire color and

terminal marking.

5. Discard or recycle old thermostat.

NOTE:

Mercury is a hazardous waste and MUST be disposed of

properly.

6. If existing thermostat cable is acceptable for application

(See Table 5), proceed to Mount Wall Thermostat and
Connect Thermostat Wires section.

If installing new thermostat cable, route as follows:

1. Drill hole for cable at location selected for thermostat.

2. Remove front panel of unit.

3. Route thermostat cable from unit’s compartment and pull

approximately 6-12 in. of cable through hole drilled in wall
for connection to thermostat terminals.

4. Strip outer casing off area of cable pulled through wall for

greater flexibility.

TABLE 5—REQUIRED THERMOSTAT CABLE TYPE

APPLICATION

THERMOSTAT

NO. OF

CONDUCTORS

REQUIRED

18 GAGE

REQUIRED

CONNECTIONS

WIRING

DIAGRAM

Air Conditioner

Robertshaw (TX400-42K)

4

G, R, Y, W

Fig. 18

TSTATPPNAC01-A

5

R, C, W/W1, Y/Y2, G

Fig. 19

TSTATPPPAC01-A

5

R, C, W/W1, Y/Y2, G

Fig. 20

Heat Pump

Honeywell (T841A1548)

6

G, R, Y, B, W2, E

Fig. 21

TSTATPPNHP01-A

8

R, C, W/W1, Y/Y2, G, B, S1, S2

Fig. 25

TSTATPPPHP01-A

8

R, G, W/W1, Y/Y2, C, B, S1, S2

Fig. 26

Fig. 17—Typical Wiring Installation

NOTE:

This diagram shows a typical wiring installation for an 036 unit with 15-kw heat. It may not reflect the wiring in unit. The actual wiring

installation to use depends on unit and electric heat requirements. (See Tables 3 and 4.) The installer must follow NEC, state, and local codes.

A95353

ON

OFF

60  AMP

ON

OFF

30  AMP

ON

OFF

40  AMP

SERVICE GROUND LUG

FOR NO. 10 AWG

AND NO. 8 AWG

NO. 6 AWG AUXILIARY

10KW HEATER NO. 2

LOAD LEADS

10KW

5KW

AUXILIARY

10KW HEATER NO. 2

LOAD LEADS

AUXILIARY
5KW HEATER NO. 1
LOAD LEADS

NO. 10 AWG AUXILIARY
5KW HEATER NO. 1
LOAD LEADS

NO. 8 AWG
COMPRESSOR LEADS

NO. 8 AWG
COMPRESSOR LEADS

COMPRESSOR

—8—

Содержание MA1A

Страница 1: ...manufactured homes These units are available in the cooling sizes shown in Table 1 The MA1A and MH1A are single package units All components including outdoor coil compressor and refrigerant tubing a...

Страница 2: ...e thermostat wire with less than the recommended number of conductors CAUTION Failure to adhere to indoor air outdoor air and exhaust air requirements as listed in the following sections will void uni...

Страница 3: ...clearance C Recommended Unit Clearances For serviceability and elimination of compressor vibration trans mission it is recommended that the sides and back of unit be installed with a minimum 1 in clea...

Страница 4: ...n See Fig 9 4 Place base template assembly over hole and mark indoor air plenum cutout in supply duct trunk measuring 13 in by 9 1 8 in See Fig 10 Mark condensate drain hose and outdoor air plenum cut...

Страница 5: ...nit and base template into floor Tighten screws flush to foam seal Overtightening screws will tip unit forward on foam seal Do NOT use any other procedure to permanently secure unit to structure 4 Cov...

Страница 6: ...panel or fuse box Refer to Table 3 and Table 4 for required circuits and recommended wire size for each circuit The unit is equipped with circuit breakers enclosed in wiring compartment This compartme...

Страница 7: ...ps Ampacity Wire Size Max Fuse Size Amps Max Wire Length Ft Amps Ampacity Wire Size Max Fuse Size Amps Max Wire Length Ft 5 018 024 030 036 23 9 29 9 10 30 80 N A N A N A N A N A 10 018 024 030 036 44...

Страница 8: ...LE TYPE APPLICATION THERMOSTAT NO OF CONDUCTORS REQUIRED 18 GAGE REQUIRED CONNECTIONS WIRING DIAGRAM Air Conditioner Robertshaw TX400 42K 4 G R Y W Fig 18 TSTATPPNAC01 A 5 R C W W1 Y Y2 G Fig 19 TSTAT...

Страница 9: ...s 4 Drill two 3 16 in mounting holes in wall where marked 5 Secure mounting base to wall with 2 screws and anchors provided making sure all wires extend through mounting base 6 Adjust wire length and...

Страница 10: ...3 Push all but approximately 2 in of thermostat cable back into wall Seal opening around cable to prevent drafts through hole which could interfere with operation of unit Fig 19 Air Conditioning Circu...

Страница 11: ...e to wall with 2 screws and anchors provided making sure all wires extend through mounting base 7 Adjust wire length and routing to allow proper closure of thermostat Strip each wire end no more than...

Страница 12: ...be adjusted NOTE Refer to Installation Instructions packaged with thermo stat for additional information D Make Low Voltage Connections at Unit Attach thermostat wires to low voltage terminal block on...

Страница 13: ...from skirting or foundation wall to entrance of outdoor air plenum See Fig 27 for a typical air tunnel 2 The condensate drain must not be allowed to drain inside air tunnel Pipe to outside of home See...

Страница 14: ...UCTBOARD 2 X 2 TREATED LUMBER Fig 28 Drain Pipe Routing A95384 NET FREE AREA SEE VENTILATION REQUIREMENTS TABLE SIZES MAY VARY AS LONG AS THE MINIMUM NET FREE OPEN AREA INCLUDING GRILLE MEETS THE REQU...

Страница 15: ...FSET FLASHING FLASHING ROOFCAP ATTIC AREA ATTIC AREA FLEX DUCT FLEX DUCT NOTE THE FLEX DUCT SHOULD BE A STRAIGHT RUN FROM UNIT TO ROOFCAP TYPICAL FRONT VIEW TYPICAL SIDE VIEW TYPICAL FRONT VIEW TYPICA...

Страница 16: ...The compressor should energize and cool air should blow through registers Once cooling test is complete return system control to OFF setting Wait 5 minutes c Set system control to HEAT and raise tempe...

Отзывы: