background image

24

EconoMi$er X (Factory-Installed Option)

PRODUCT DESCRIPTION 
The EconoMi$er

®

 X system is an expandable economizer con

-

trol system, which includes a W7220 economizer module (con

-

troller)  with  an  LCD  and  keypad  (see  Fig.  44). The  W7220

module can be configured with optional sensors.

Fig. 44 — W7220 Economizer Module

The W7220 economizer module can be used as a stand-alone econo

-

mizer module wired directly to a commercial set-back space thermo

-

stat and sensors to provide outside air dry-bulb economizer control.

The W7220 economizer module can be connected to optional sen

-

sors for single or differential enthalpy control. The W7220 econo

-

mizer module provides power and communications for the sensors.

The W7220  economizer  module  automatically  detects  sensors  by

polling  to  determine  which  sensors  are  present.  If  a  sensor  loses

communications after it has been detected, the W7220 economizer

controller indicates a device fail error on its LCD.
SYSTEM COMPONENTS
The  EconoMi$er  X  system  includes  an  economizer  module,

20k mixed air sensor, damper actuator, and either a 20k out

-

door air temperature sensor or S-Bus enthalpy sensors.

Economizer Module

The module is the core of the EconoMi$er X system. The mod

-

ule is mounted in the unit’s control box, and includes the user

interface for the system. The W7220 economizer module pro

-

vides the basic inputs and outputs to provide simple economiz

-

er control. When used with the optional sensors, the economiz

-

er module provides more advanced economizer functionality.

S-Bus Enthalpy Control Sensors 

The sensor is a combination temperature and humidity sensor

which is powered by and communicates on the S-Bus. Up to

3 sensors  may  be  configured  with  the  W7220  economizer

module.

CO

2

 Sensor (optional)

The  sensor  can  be  added  for  Demand  Controlled Ventilation

(DCV). 
SPECIFICATIONS

W7220 Economizer Module 

The module is designed for use with 2 to 10 vdc or bus com

-

municating  actuator. The  module  includes  terminals  for  CO

2

sensor, Mixed Air sensor, and an Outdoor Dry Bulb sensor. En

-

thalpy and other options are available with bus sensors.

User Interface

Provides status for normal operation, setup parameters, check

-

out tests, and alarm and error conditions with a 2-line 16 char

-

acter LCD display and 4 button keypad.

Electrical

Rated Voltage —

 

20 to 30 vac RMS, 50/60 Hz

Transformer — 100 va maximum system input

Nominal Power Consumption (at 24 vac, 60 Hz) — 11.5 VA

without sensors or actuators

Relay Digital Output Rating at 30 vac (maximum power from

Class 2 input only) — 1.5A run:

3.5A inrush at 0.45PF (200,000 cycles) or

7.5A inrush at 0.45PF (100,000 cycles)

External Sensors Power Output — 21 vdc ± 5% at 48mA

INPUTS

Sensors

NOTE:  A  Mixed  Air  (MA)  analog  sensor  is  required  on  all

W7220  units;  either  an  Outdoor Air  (OA)  sensor  for  dry  bulb

change  over  or  an  OA  bus  sensor  for  outdoor  enthalpy  change

over is required in addition to the MA sensor. An additional Re

-

turn Air (RA) bus sensor can be added to the system for differen

-

tial  enthalpy  or  dry  bulb  changeover.  For  differential  dry  bulb

changeover, a 20k ohm sensor is required in the OA and a bus sen

-

sor in the RA. DIP switch on RA bus sensor must be set in the RA

position.

Dry Bulb Temperature (optional) and Mixed Air (required), 

20k NTC

2-wire (18 to 22 AWG);

Temperature range –40°F to 150°F (–40°C to 65°C)

Temperature accuracy –0°F/+2°F

Temperature and Humidity, C7400S1000 (optional)

S-Bus; 2-wire (18 to 22 AWG)

Temperature: range –40°F to 150°F (–40°C to 65°C)

Temperature accuracy –0°F/+2°F

Humidity: range 0 to 100% RH with 5% accuracy.

NOTE: Up to three (3) S-Bus sensors may be connected to the

W7220 economizer module. For outdoor air (OA), return air (RA)

and discharge (supply) air (DA).

4 Binary Inputs

1-wire 24 vac + common GND (see page 26 for wiring details). 

24 vac power supply

20 to 30 vac 50/60Hz; 100 VA Class 2 transformer. 
OUTPUTS

Actuator Signal:

2-10 vdc; minimum actuator impedance is 2k ohm; bus 2Hwire

output for bus communicating actuators.

Exhaust fan, Y1, Y2 and AUX1 O:

All Relay Outputs (at 30 vac):

Running: 1.5A maximum

Inrush: 7.5A maximum

IMPORTANT: All inputs and outputs must be Class 2 wiring.

Содержание Legacy 547K 14

Страница 1: ...UT FUSES LOW VOLTAGE CONTROL CONNECTIONS CONTROL AND POWER WIRING DIAGRAMS EconoMi er X Factory Installed Option 24 PRODUCT DESCRIPTION SYSTEM COMPONENTS SPECIFICATIONS INPUTS OUTPUTS ENVIRONMENTAL EC...

Страница 2: ...nt DANGER ELECTRICAL SHOCK HAZARD Failure to follow this warning will result in personal injury or death Before performing service or maintenance operations on unit turn off main power switch to unit...

Страница 3: ...Coil Options Round Tube Plate Fin Condenser Evaporator Hail Guard A Al Cu Al Cu B Precoat Al Cu Al Cu C E coat Al Cu Al Cu D E coat Al Cu E coat Al Cu E Cu Cu Al Cu F Cu Cu Cu Cu M Al Cu Al Cu Louver...

Страница 4: ...4 Fig 2 547K 14 Unit Dimensional Drawing...

Страница 5: ...5 Fig 2 547K 14 Unit Dimensional Drawing cont...

Страница 6: ...ounting system that provides adequate height to allow for removal and disposal of frost and ice that will form during the heating defrost mode as well as allow installation of condensate trap per requ...

Страница 7: ...ter flashing as shown Ductwork must be attached to curb and not to the unit SLAB MOUNT HORIZONTAL UNITS ONLY Provide a level concrete slab that extends a minimum of 6 in 150 mm beyond unit cabinet Ins...

Страница 8: ...8 Fig 5 547K 14 Roof Curb Details...

Страница 9: ...ssary Fig 7 Retrofit Installation Dimensions If the alternative condensate drain location through the bottom of the unit is used in conjunction with a retrofit curb the hole in the curb must be moved...

Страница 10: ...filter access opening and assemble per the steps out lined in Economizer and Two Position Hood Setup on page 10 Fig 9 Typical Access Panel Locations Fig 10 Economizer Hood Package Location ECONOMIZER...

Страница 11: ...t 25 mm in 3 m of run Do not use a pipe size smaller than the unit connection 3 4 in Step 10 Make Electrical Connections NOTE Check all factory and field electrical connections for tight ness Field su...

Страница 12: ...how the wire routings If the field disconnect is larger than 100 A it must be attached to the unit using accessory CRDISBKT001A00 disconnect switch bracket see Fig 19 Follow the instructions provided...

Страница 13: ...ithin 2 and the current within 10 Use the following formula to de termine the percent of voltage imbalance Example Supply voltage is 230 3 60 Determine maximum deviation from average voltage AB 227 22...

Страница 14: ...hex screws on the NFD enclosure 12 Re install the unit front panel Fig 23 Location of Non Fused Disconnect Enclosure Fig 24 Handle and Shaft Assembly for NFD UNITS WITHOUT FACTORY INSTALLED NON FUSED...

Страница 15: ...x and mounted on a bracket behind the convenience outlet access is through the unit s control box access panel See Fig 25 The primary leads to the convenience outlet transformer are not factory connec...

Страница 16: ...ghtness of connector lock nuts before connecting elec trical conduits Field supplied and field installed liquid tight conduit connectors and conduit may be attached to the connectors on the basepan Pu...

Страница 17: ...33 Defrost Control Board Arrangement Reversing Valve Control The DFB has 2 outputs for unit reversing valve control Opera tion of the reversing valves is based on internal logic this application does...

Страница 18: ...s SW1 and SW2 see Fig 35 and Table 4 The de fault run period is 60 minutes Fig 35 DIP Switch Settings Defrost Board Table 3 547K Defrost Board I O and Jumper Configurations POINT NAME TYPE OF I O CONN...

Страница 19: ...rough ceramic insulators line break limit switches and a control contactor Heater modules are installed in the compartment below the in door supply fan outlet Access is through the electric heat acces...

Страница 20: ...60 A fuse regardless of actual heater ampacity so only 60 A fuses are necessary SINGLE POINT BOXES WITHOUT FUSES Unit heater applications not requiring supplemental fuses re quire a special single po...

Страница 21: ...21 Fig 41 Typical Control Wiring Diagram Electromechanical with W7220 Controller...

Страница 22: ...22 Fig 42 Typical Power Wiring Diagram 208 230 460 3 60 Unit Shown...

Страница 23: ...23 Fig 43 Typical Power Wiring Diagram 575 3 60 Unit Shown...

Страница 24: ...le includes terminals for CO2 sensor Mixed Air sensor and an Outdoor Dry Bulb sensor En thalpy and other options are available with bus sensors User Interface Provides status for normal operation setu...

Страница 25: ...24 Part 6 Table 5 Economizer Module Left Hand Terminal Blocks LABEL TYPE DESCRIPTION Top Left Terminal Block MAT MAT 20k NTC and COM Mixed Air Temperature Sensor Polarity Insensitive Connection OAT OA...

Страница 26: ...g 48 are used to scroll through the menus and menu items select menu items and to change parameter and configuration settings To use the keypad when working with menus Press the Up arrow button to mov...

Страница 27: ...rs MA or MAT indicating a mixed air temperature sensor location before the cooling coil This unit application has the control sensor locat ed after the cooling coil in the fan section where it is desi...

Страница 28: ...ture Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F 40 F to 140 F 40 C to 60 C OUTSIDE AIR TEMP Displays measured value of outdoor air temperature...

Страница 29: ...TILATION MINIMUM POSITION AT LOW SPEED Only displays if unit is set for 2 or 3 speed and CO2 is not used If using 2 speed with 1 heat and 1 cool then set for HEATING ventilation If using 3 speed with...

Страница 30: ...e NOTE If using 2 speed fan mode you must program CONV mode for W Shutdown is not available in 2 speed fan mode g In HP O B mode HP O energize heat pump on Cool default HP B energize heat pump on heat...

Страница 31: ...just for an out of calibration temperature sensor 2SP FAN DELAY 5 Minutes 0 to 20 minutes in 1 minute increments TIME DELAY ON SECOND STAGE ECONOMIZING When in economizing mode this is the delay for t...

Страница 32: ...TUATOR STALLED Actuator stopped before achieving commanded position NOTE S a Table 9 illustrates the complete hierarchy Your menu parameters may be different depending on your configuration For exampl...

Страница 33: ...Economizer Operation FAN TYPE 2SPEED INPUTS OUTPUTS DEMAND CONTROLLED VENTILATION DCV OUTSIDE AIR GOOD TO ECONOMIZE W HEAT ON COOL Y1 IN COOL Y2 IN COOL Y1 OUT COOL Y2 OUT FAN SPEED reference only DAM...

Страница 34: ...en all of the OA conditions are above the selected bound ary the conditions are not good to economize and the mode is set to NO Figure 49 shows the 5 current boundaries There is also a high limit boun...

Страница 35: ...e to the Alarms menu at any time Clearing Alarms Once the alarm has been identified and the cause has been re moved e g replaced faulty sensor the alarm can be cleared from the display To clear an ala...

Страница 36: ...l and Medium Rooftop Units 2 to 25 Tons for discussions on additional control features of these smoke detectors including multiple unit coordination Fig 50 Return Air Smoke Detector Shipping Position...

Страница 37: ...ries Step 13 Fan Speed Set Up NOTE The Indoor Fan motor is equipped with an internal protec tion relay that is designed to disable unit operation if it detects a problem See Typical Wiring Diagram Fig...

Страница 38: ...4 6 1 6 4 6 8 7 2 7 6 8 0 8 4 8 8 9 2 0 4 0 6 6 5 6 8 7 2 7 5 7 9 8 3 8 7 9 1 0 4 0 8 6 9 7 2 7 6 7 9 8 2 8 6 9 0 0 4 1 0 7 3 7 6 7 9 8 2 8 6 0 4 1 2 7 6 7 9 8 2 8 6 0 4 1 4 8 0 8 3 8 6 0 4 1 6 1 8 2...

Страница 39: ...ing Valve Energized Check Valve A Closed Check Valve B Open Check Valve C Open Check Valve D Open Check Valve E Open Check Valve F Closed Check Valve G Closed Table 14 547K 14 Heating Mode COMPONENT S...

Страница 40: ...l installation of the unit Refer to the unit s Service Manual for detailed Pre Start and Start Up instructions Download the latest versions from HVAC Partners www hvacpartners com LPS LOC HPS Indoor C...

Страница 41: ......

Страница 42: ...reserves the right to change at any time specifications and designs without notice and without obligations Replaces New 2022 Carrier Cat No 04 53547013 01 Edition Date 6 22 Printed in U S A Form No I...

Страница 43: ...N _____ Check that indoor air filters are clean and in place Y N _____ Check that outdoor air inlet screens are in place Y N _____ Verify that unit is level Y N _____ Verify that fan assembly is free...

Страница 44: ...r Cat No 04 53547013 01 Edition Date 6 22 Printed in U S A Form No II547K 14 01 PRESSURES Refrigerant Suction ____________ PSIG Refrigerant Discharge ____________ PSIG Verify Refrigerant Charge using...

Отзывы: