background image

35

CHECKOUT
Inspect all wiring connections at the economizer module’s ter

-

minals, and verify compliance with the installation wiring dia

-

grams.

For checkout, review the Status of each configured parameter

and perform the Checkout tests.

NOTE:  For  information  about  menu  navigation  and  use  of  the

keypad, see Interface Overview on page 26.

Power Up

After the W7220 module is mounted and wired, apply power.

Initial Menu Display

On  initial  start  up,  Honeywell  displays  on  the  first  line  and

Economizer W7220 on the second line. After a brief pause, the

revision of the software appears on the first line and the second

line will be blank.

Power Loss (Outage or Brownout)

All set points and advanced settings are restored after any pow

-

er loss or interruption.

NOTE: All settings are stored in non-volatile flash memory.

Status

Use the Status menu (see Table 9) to check the parameter val

-

ues for the various devices and sensors configured.

NOTE:  For  information  about  menu  navigation  and  use  of  the

keypad, see Interface Overview on page 26.

Checkout Tests

Use the Checkout menu (on page 31) to test the damper opera

-

tion and any  configured outputs. Only items that are config

-

ured are shown in the Checkout menu.

NOTE:  For  information  about  menu  navigation  and  use  of  the

keypad, see Interface Overview on page 26.

To perform a Checkout test:

1. Scroll to the desired test in the Checkout menu using the

▲ and ▼ buttons. 

2. Press the 

 (Enter) button to select the item. 

3. RUN? appears. 

4. Press the 

 (Enter) button to start the test. 

5. The unit pauses and then displays IN PROGRESS. 

6. When the test is complete, DONE appears. 

7. When all  desired  parameters have  been  tested,  press the

 (Menu Up) button to end the test.

The Checkout tests can all be performed at the time of installa

-

tion or at any time during the operation of the system as a test

that the system is operable.

TROUBLESHOOTING

Alarms

The economizer module provides alarm messages that display

on the 2-line LCD.

NOTE: Upon power up, the module waits 60 minutes before

checking  for  alarms. This  allows  time  for  all  the  configured

devices  (e.g.  sensors,  actuator)  to  become  operational.  The

exception is the SAT sensor which will alarm immediately.

If one or more alarms are present and there has been no keypad

activity for at least 5 minutes, the Alarms menu displays and

cycles through the active alarms.

You can also navigate to the Alarms menu at any time.

Clearing Alarms

Once the alarm has been identified and the cause has been re

-

moved (e.g. replaced faulty sensor), the alarm can be cleared

from the display.

To clear an alarm, perform the following:

1. Navigate to the desired alarm.

2. Press the 

 (Enter) button.

3. ERASE? displays.

4. Press the 

 (Enter) button.

5. ALARM ERASED displays.

6. Press  the 

  (Menu  up/Exit)  button  to  complete  the

action and return to the previous menu.

NOTE: If the alarm still exists after clearing it, it is redisplayed

within 5 seconds.

SMOKE DETECTORS
Smoke detectors are available as factory-installed options on

547K models. Smoke detectors may be specified for supply air

only,  for  return  air  without  or  with  economizer,  or  in

combination  of  supply  air  and  return  air.  All  components

necessary for operation are factory-provided and mounted. The

unit  is  factory-configured  for  immediate  smoke  detector

shutdown operation; additional wiring or modifications to unit

terminal  board  may  be  necessary  to  complete  the  unit  and

smoke detector configuration to meet project requirements.

Units  equipped  with  factory-optional  return-air  smoke  detec

-

tors  require  a  relocation  of  the  sensor  module  at  unit

installation. See Fig. 50 for the as-shipped location.
COMPLETING  INSTALLATION  OF  RETURN-AIR

SMOKE SENSOR
1. Unscrew the 2 screws holding the return-air smoke detec

-

tor assembly. See Fig. 51, Step 1.

2. Save the screws.

3. Turn the assembly 90 degrees and then rotate end to end.

Make  sure  that  the  elbow  fitting  is  pointing  down.  See

Fig. 51, Step 2.

4. Screw the sensor and detector plate into its operating posi

-

tion using screws from Step 1. See Fig. 51, Step 3.

5. Connect  the  flexible  tube  on  the  sampling  inlet  to  the

sampling tube on the basepan.

WARNING

ELECTRIC SHOCK HAZARD

Failure  to  follow  this  warning  could  result  in  personal

injury, property damage, or death. 

Before  performing  service  or  maintenance  operations  on

unit, always turn off main power switch to unit and install

lock(s) and lockout tag(s). Unit may have more than one

power  switch.  Ensure  electrical  service  to  rooftop  unit

agrees with voltage and amperage listed on the unit rating

plate.

If any wiring changes are required, first be sure to remove

power from the economizer module before starting work.

Pay particular attention to verifying the power connection

(24 vac).

CAUTION

EQUIPMENT DAMAGE HAZARD

Failure  to  follow  this  caution  may  result  in  equipment

damage.

Be sure to allow enough time for compressor start-up and

shutdown between checkout tests so that you do not short-

cycle the compressors.

Содержание Legacy 547K 14

Страница 1: ...UT FUSES LOW VOLTAGE CONTROL CONNECTIONS CONTROL AND POWER WIRING DIAGRAMS EconoMi er X Factory Installed Option 24 PRODUCT DESCRIPTION SYSTEM COMPONENTS SPECIFICATIONS INPUTS OUTPUTS ENVIRONMENTAL EC...

Страница 2: ...nt DANGER ELECTRICAL SHOCK HAZARD Failure to follow this warning will result in personal injury or death Before performing service or maintenance operations on unit turn off main power switch to unit...

Страница 3: ...Coil Options Round Tube Plate Fin Condenser Evaporator Hail Guard A Al Cu Al Cu B Precoat Al Cu Al Cu C E coat Al Cu Al Cu D E coat Al Cu E coat Al Cu E Cu Cu Al Cu F Cu Cu Cu Cu M Al Cu Al Cu Louver...

Страница 4: ...4 Fig 2 547K 14 Unit Dimensional Drawing...

Страница 5: ...5 Fig 2 547K 14 Unit Dimensional Drawing cont...

Страница 6: ...ounting system that provides adequate height to allow for removal and disposal of frost and ice that will form during the heating defrost mode as well as allow installation of condensate trap per requ...

Страница 7: ...ter flashing as shown Ductwork must be attached to curb and not to the unit SLAB MOUNT HORIZONTAL UNITS ONLY Provide a level concrete slab that extends a minimum of 6 in 150 mm beyond unit cabinet Ins...

Страница 8: ...8 Fig 5 547K 14 Roof Curb Details...

Страница 9: ...ssary Fig 7 Retrofit Installation Dimensions If the alternative condensate drain location through the bottom of the unit is used in conjunction with a retrofit curb the hole in the curb must be moved...

Страница 10: ...filter access opening and assemble per the steps out lined in Economizer and Two Position Hood Setup on page 10 Fig 9 Typical Access Panel Locations Fig 10 Economizer Hood Package Location ECONOMIZER...

Страница 11: ...t 25 mm in 3 m of run Do not use a pipe size smaller than the unit connection 3 4 in Step 10 Make Electrical Connections NOTE Check all factory and field electrical connections for tight ness Field su...

Страница 12: ...how the wire routings If the field disconnect is larger than 100 A it must be attached to the unit using accessory CRDISBKT001A00 disconnect switch bracket see Fig 19 Follow the instructions provided...

Страница 13: ...ithin 2 and the current within 10 Use the following formula to de termine the percent of voltage imbalance Example Supply voltage is 230 3 60 Determine maximum deviation from average voltage AB 227 22...

Страница 14: ...hex screws on the NFD enclosure 12 Re install the unit front panel Fig 23 Location of Non Fused Disconnect Enclosure Fig 24 Handle and Shaft Assembly for NFD UNITS WITHOUT FACTORY INSTALLED NON FUSED...

Страница 15: ...x and mounted on a bracket behind the convenience outlet access is through the unit s control box access panel See Fig 25 The primary leads to the convenience outlet transformer are not factory connec...

Страница 16: ...ghtness of connector lock nuts before connecting elec trical conduits Field supplied and field installed liquid tight conduit connectors and conduit may be attached to the connectors on the basepan Pu...

Страница 17: ...33 Defrost Control Board Arrangement Reversing Valve Control The DFB has 2 outputs for unit reversing valve control Opera tion of the reversing valves is based on internal logic this application does...

Страница 18: ...s SW1 and SW2 see Fig 35 and Table 4 The de fault run period is 60 minutes Fig 35 DIP Switch Settings Defrost Board Table 3 547K Defrost Board I O and Jumper Configurations POINT NAME TYPE OF I O CONN...

Страница 19: ...rough ceramic insulators line break limit switches and a control contactor Heater modules are installed in the compartment below the in door supply fan outlet Access is through the electric heat acces...

Страница 20: ...60 A fuse regardless of actual heater ampacity so only 60 A fuses are necessary SINGLE POINT BOXES WITHOUT FUSES Unit heater applications not requiring supplemental fuses re quire a special single po...

Страница 21: ...21 Fig 41 Typical Control Wiring Diagram Electromechanical with W7220 Controller...

Страница 22: ...22 Fig 42 Typical Power Wiring Diagram 208 230 460 3 60 Unit Shown...

Страница 23: ...23 Fig 43 Typical Power Wiring Diagram 575 3 60 Unit Shown...

Страница 24: ...le includes terminals for CO2 sensor Mixed Air sensor and an Outdoor Dry Bulb sensor En thalpy and other options are available with bus sensors User Interface Provides status for normal operation setu...

Страница 25: ...24 Part 6 Table 5 Economizer Module Left Hand Terminal Blocks LABEL TYPE DESCRIPTION Top Left Terminal Block MAT MAT 20k NTC and COM Mixed Air Temperature Sensor Polarity Insensitive Connection OAT OA...

Страница 26: ...g 48 are used to scroll through the menus and menu items select menu items and to change parameter and configuration settings To use the keypad when working with menus Press the Up arrow button to mov...

Страница 27: ...rs MA or MAT indicating a mixed air temperature sensor location before the cooling coil This unit application has the control sensor locat ed after the cooling coil in the fan section where it is desi...

Страница 28: ...ture Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F 40 F to 140 F 40 C to 60 C OUTSIDE AIR TEMP Displays measured value of outdoor air temperature...

Страница 29: ...TILATION MINIMUM POSITION AT LOW SPEED Only displays if unit is set for 2 or 3 speed and CO2 is not used If using 2 speed with 1 heat and 1 cool then set for HEATING ventilation If using 3 speed with...

Страница 30: ...e NOTE If using 2 speed fan mode you must program CONV mode for W Shutdown is not available in 2 speed fan mode g In HP O B mode HP O energize heat pump on Cool default HP B energize heat pump on heat...

Страница 31: ...just for an out of calibration temperature sensor 2SP FAN DELAY 5 Minutes 0 to 20 minutes in 1 minute increments TIME DELAY ON SECOND STAGE ECONOMIZING When in economizing mode this is the delay for t...

Страница 32: ...TUATOR STALLED Actuator stopped before achieving commanded position NOTE S a Table 9 illustrates the complete hierarchy Your menu parameters may be different depending on your configuration For exampl...

Страница 33: ...Economizer Operation FAN TYPE 2SPEED INPUTS OUTPUTS DEMAND CONTROLLED VENTILATION DCV OUTSIDE AIR GOOD TO ECONOMIZE W HEAT ON COOL Y1 IN COOL Y2 IN COOL Y1 OUT COOL Y2 OUT FAN SPEED reference only DAM...

Страница 34: ...en all of the OA conditions are above the selected bound ary the conditions are not good to economize and the mode is set to NO Figure 49 shows the 5 current boundaries There is also a high limit boun...

Страница 35: ...e to the Alarms menu at any time Clearing Alarms Once the alarm has been identified and the cause has been re moved e g replaced faulty sensor the alarm can be cleared from the display To clear an ala...

Страница 36: ...l and Medium Rooftop Units 2 to 25 Tons for discussions on additional control features of these smoke detectors including multiple unit coordination Fig 50 Return Air Smoke Detector Shipping Position...

Страница 37: ...ries Step 13 Fan Speed Set Up NOTE The Indoor Fan motor is equipped with an internal protec tion relay that is designed to disable unit operation if it detects a problem See Typical Wiring Diagram Fig...

Страница 38: ...4 6 1 6 4 6 8 7 2 7 6 8 0 8 4 8 8 9 2 0 4 0 6 6 5 6 8 7 2 7 5 7 9 8 3 8 7 9 1 0 4 0 8 6 9 7 2 7 6 7 9 8 2 8 6 9 0 0 4 1 0 7 3 7 6 7 9 8 2 8 6 0 4 1 2 7 6 7 9 8 2 8 6 0 4 1 4 8 0 8 3 8 6 0 4 1 6 1 8 2...

Страница 39: ...ing Valve Energized Check Valve A Closed Check Valve B Open Check Valve C Open Check Valve D Open Check Valve E Open Check Valve F Closed Check Valve G Closed Table 14 547K 14 Heating Mode COMPONENT S...

Страница 40: ...l installation of the unit Refer to the unit s Service Manual for detailed Pre Start and Start Up instructions Download the latest versions from HVAC Partners www hvacpartners com LPS LOC HPS Indoor C...

Страница 41: ......

Страница 42: ...reserves the right to change at any time specifications and designs without notice and without obligations Replaces New 2022 Carrier Cat No 04 53547013 01 Edition Date 6 22 Printed in U S A Form No I...

Страница 43: ...N _____ Check that indoor air filters are clean and in place Y N _____ Check that outdoor air inlet screens are in place Y N _____ Verify that unit is level Y N _____ Verify that fan assembly is free...

Страница 44: ...r Cat No 04 53547013 01 Edition Date 6 22 Printed in U S A Form No II547K 14 01 PRESSURES Refrigerant Suction ____________ PSIG Refrigerant Discharge ____________ PSIG Verify Refrigerant Charge using...

Отзывы: