Fig. 6 — Rigging Details

Step 6 — Rig and Place Unit

Keep unit upright and do not drop. Spreader bars are not re

-

quired.

 

Rollers may be used to move unit across a roof. Level

by using unit frame as a reference. See Table and Fig. for

additional information.

Lifting holes are provided in base rails as shown in Fig. 6. Re

-

fer to rigging instructions on unit.

Rigging  materials  under  unit  (cardboard  or  wood  to  prevent

base pan damage) must be removed PRIOR to placing the unit

on the roof curb.

When using the standard side drain connection, ensure the red

plug in the alternate bottom connection is tight. Do this before

setting  the  unit  in place. The red  drain  pan  can  be  tightened

with a 1/2 in. square socket drive extension. For further details

see Install External Condensate Trap and Line on page 11.

Before  setting  the  unit  onto  the  curb,  recheck  gasketing  on

curb.

POSITIONING ON CURB
For full perimeter curbs CRRFCURB074A00 and 075A00, the

clearance  between  the  roof  curb  and  the  front  and  rear  base

rails  should  be  1/4  in.  (6.4  mm). The  clearance  between  the

curb and the end base rails should be 1/2 in. (13 mm). For ret

-

rofit applications with curbs CRRFCURB003A01 and 4A01,

the unit should be positioned as shown in Fig. 7. Maintain the

15-1/2  in.  (394  mm)  and  8-5/8  in.  (220  mm)  clearances  and

allow the 22-5/16 in. (567 mm) dimension to float if necessary.

Fig. 7 — Retrofit Installation Dimensions

If the alternative condensate drain location through the bottom

of the unit is used in conjunction with a retrofit curb, the hole

in the curb must be moved 12-1/2 in. (320 mm) towards the

duct end of the unit. See Fig. 8.

Although unit is weatherproof, guard against water from higher

level runoff and overhangs.

Remove all shipping materials and top skid. Remove extra cen

-

ter post from the condenser end of the unit so that the condens

-

er end of the unit matches Fig. 16 and 17. Recycle or dispose of

all shipping materials.

Fig. 8 — Alternative Condensate Drain Hole Positions

Detail “A”

See Detail “A”

(914-1371)

36”-54” 

“B”

“A”

“A”

“C”

Place All Gasket in Place Before Placing
Unit on Roof Curb.

Duct End

UNIT

MAX WEIGHT

DIMENSIONS

A

B

C

lb

kg

in.

mm

in.

mm

in.

mm

547K*14

1901

862

116.0

2945

57.0

1450

59.5

1510

NOTES:

1. Dimensions in () are in millimeters.

2. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use

wooden top to prevent rigging straps from damaging unit.

CAUTION

UNIT DAMAGE HAZARD

Failure  to  follow  this  caution  may  result  in  equipment

damage.

All  panels  must  be  in  place  when  rigging.  Unit  is  not

designed  for  handling  by  fork  truck  when  packaging

is removed.

If using top crate as spreader bar, once unit is set, carefully

lower wooden crate off building roof top to ground. Ensure

that no people or obstructions are below prior to lowering

the crate.

8-5/8

22-5/16

15-1/2

Original 
Position

New Position
(Moved 12.5 in.)

Содержание Legacy 547K 14

Страница 1: ...UT FUSES LOW VOLTAGE CONTROL CONNECTIONS CONTROL AND POWER WIRING DIAGRAMS EconoMi er X Factory Installed Option 24 PRODUCT DESCRIPTION SYSTEM COMPONENTS SPECIFICATIONS INPUTS OUTPUTS ENVIRONMENTAL EC...

Страница 2: ...nt DANGER ELECTRICAL SHOCK HAZARD Failure to follow this warning will result in personal injury or death Before performing service or maintenance operations on unit turn off main power switch to unit...

Страница 3: ...Coil Options Round Tube Plate Fin Condenser Evaporator Hail Guard A Al Cu Al Cu B Precoat Al Cu Al Cu C E coat Al Cu Al Cu D E coat Al Cu E coat Al Cu E Cu Cu Al Cu F Cu Cu Cu Cu M Al Cu Al Cu Louver...

Страница 4: ...4 Fig 2 547K 14 Unit Dimensional Drawing...

Страница 5: ...5 Fig 2 547K 14 Unit Dimensional Drawing cont...

Страница 6: ...ounting system that provides adequate height to allow for removal and disposal of frost and ice that will form during the heating defrost mode as well as allow installation of condensate trap per requ...

Страница 7: ...ter flashing as shown Ductwork must be attached to curb and not to the unit SLAB MOUNT HORIZONTAL UNITS ONLY Provide a level concrete slab that extends a minimum of 6 in 150 mm beyond unit cabinet Ins...

Страница 8: ...8 Fig 5 547K 14 Roof Curb Details...

Страница 9: ...ssary Fig 7 Retrofit Installation Dimensions If the alternative condensate drain location through the bottom of the unit is used in conjunction with a retrofit curb the hole in the curb must be moved...

Страница 10: ...filter access opening and assemble per the steps out lined in Economizer and Two Position Hood Setup on page 10 Fig 9 Typical Access Panel Locations Fig 10 Economizer Hood Package Location ECONOMIZER...

Страница 11: ...t 25 mm in 3 m of run Do not use a pipe size smaller than the unit connection 3 4 in Step 10 Make Electrical Connections NOTE Check all factory and field electrical connections for tight ness Field su...

Страница 12: ...how the wire routings If the field disconnect is larger than 100 A it must be attached to the unit using accessory CRDISBKT001A00 disconnect switch bracket see Fig 19 Follow the instructions provided...

Страница 13: ...ithin 2 and the current within 10 Use the following formula to de termine the percent of voltage imbalance Example Supply voltage is 230 3 60 Determine maximum deviation from average voltage AB 227 22...

Страница 14: ...hex screws on the NFD enclosure 12 Re install the unit front panel Fig 23 Location of Non Fused Disconnect Enclosure Fig 24 Handle and Shaft Assembly for NFD UNITS WITHOUT FACTORY INSTALLED NON FUSED...

Страница 15: ...x and mounted on a bracket behind the convenience outlet access is through the unit s control box access panel See Fig 25 The primary leads to the convenience outlet transformer are not factory connec...

Страница 16: ...ghtness of connector lock nuts before connecting elec trical conduits Field supplied and field installed liquid tight conduit connectors and conduit may be attached to the connectors on the basepan Pu...

Страница 17: ...33 Defrost Control Board Arrangement Reversing Valve Control The DFB has 2 outputs for unit reversing valve control Opera tion of the reversing valves is based on internal logic this application does...

Страница 18: ...s SW1 and SW2 see Fig 35 and Table 4 The de fault run period is 60 minutes Fig 35 DIP Switch Settings Defrost Board Table 3 547K Defrost Board I O and Jumper Configurations POINT NAME TYPE OF I O CONN...

Страница 19: ...rough ceramic insulators line break limit switches and a control contactor Heater modules are installed in the compartment below the in door supply fan outlet Access is through the electric heat acces...

Страница 20: ...60 A fuse regardless of actual heater ampacity so only 60 A fuses are necessary SINGLE POINT BOXES WITHOUT FUSES Unit heater applications not requiring supplemental fuses re quire a special single po...

Страница 21: ...21 Fig 41 Typical Control Wiring Diagram Electromechanical with W7220 Controller...

Страница 22: ...22 Fig 42 Typical Power Wiring Diagram 208 230 460 3 60 Unit Shown...

Страница 23: ...23 Fig 43 Typical Power Wiring Diagram 575 3 60 Unit Shown...

Страница 24: ...le includes terminals for CO2 sensor Mixed Air sensor and an Outdoor Dry Bulb sensor En thalpy and other options are available with bus sensors User Interface Provides status for normal operation setu...

Страница 25: ...24 Part 6 Table 5 Economizer Module Left Hand Terminal Blocks LABEL TYPE DESCRIPTION Top Left Terminal Block MAT MAT 20k NTC and COM Mixed Air Temperature Sensor Polarity Insensitive Connection OAT OA...

Страница 26: ...g 48 are used to scroll through the menus and menu items select menu items and to change parameter and configuration settings To use the keypad when working with menus Press the Up arrow button to mov...

Страница 27: ...rs MA or MAT indicating a mixed air temperature sensor location before the cooling coil This unit application has the control sensor locat ed after the cooling coil in the fan section where it is desi...

Страница 28: ...ture Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F 40 F to 140 F 40 C to 60 C OUTSIDE AIR TEMP Displays measured value of outdoor air temperature...

Страница 29: ...TILATION MINIMUM POSITION AT LOW SPEED Only displays if unit is set for 2 or 3 speed and CO2 is not used If using 2 speed with 1 heat and 1 cool then set for HEATING ventilation If using 3 speed with...

Страница 30: ...e NOTE If using 2 speed fan mode you must program CONV mode for W Shutdown is not available in 2 speed fan mode g In HP O B mode HP O energize heat pump on Cool default HP B energize heat pump on heat...

Страница 31: ...just for an out of calibration temperature sensor 2SP FAN DELAY 5 Minutes 0 to 20 minutes in 1 minute increments TIME DELAY ON SECOND STAGE ECONOMIZING When in economizing mode this is the delay for t...

Страница 32: ...TUATOR STALLED Actuator stopped before achieving commanded position NOTE S a Table 9 illustrates the complete hierarchy Your menu parameters may be different depending on your configuration For exampl...

Страница 33: ...Economizer Operation FAN TYPE 2SPEED INPUTS OUTPUTS DEMAND CONTROLLED VENTILATION DCV OUTSIDE AIR GOOD TO ECONOMIZE W HEAT ON COOL Y1 IN COOL Y2 IN COOL Y1 OUT COOL Y2 OUT FAN SPEED reference only DAM...

Страница 34: ...en all of the OA conditions are above the selected bound ary the conditions are not good to economize and the mode is set to NO Figure 49 shows the 5 current boundaries There is also a high limit boun...

Страница 35: ...e to the Alarms menu at any time Clearing Alarms Once the alarm has been identified and the cause has been re moved e g replaced faulty sensor the alarm can be cleared from the display To clear an ala...

Страница 36: ...l and Medium Rooftop Units 2 to 25 Tons for discussions on additional control features of these smoke detectors including multiple unit coordination Fig 50 Return Air Smoke Detector Shipping Position...

Страница 37: ...ries Step 13 Fan Speed Set Up NOTE The Indoor Fan motor is equipped with an internal protec tion relay that is designed to disable unit operation if it detects a problem See Typical Wiring Diagram Fig...

Страница 38: ...4 6 1 6 4 6 8 7 2 7 6 8 0 8 4 8 8 9 2 0 4 0 6 6 5 6 8 7 2 7 5 7 9 8 3 8 7 9 1 0 4 0 8 6 9 7 2 7 6 7 9 8 2 8 6 9 0 0 4 1 0 7 3 7 6 7 9 8 2 8 6 0 4 1 2 7 6 7 9 8 2 8 6 0 4 1 4 8 0 8 3 8 6 0 4 1 6 1 8 2...

Страница 39: ...ing Valve Energized Check Valve A Closed Check Valve B Open Check Valve C Open Check Valve D Open Check Valve E Open Check Valve F Closed Check Valve G Closed Table 14 547K 14 Heating Mode COMPONENT S...

Страница 40: ...l installation of the unit Refer to the unit s Service Manual for detailed Pre Start and Start Up instructions Download the latest versions from HVAC Partners www hvacpartners com LPS LOC HPS Indoor C...

Страница 41: ......

Страница 42: ...reserves the right to change at any time specifications and designs without notice and without obligations Replaces New 2022 Carrier Cat No 04 53547013 01 Edition Date 6 22 Printed in U S A Form No I...

Страница 43: ...N _____ Check that indoor air filters are clean and in place Y N _____ Check that outdoor air inlet screens are in place Y N _____ Verify that unit is level Y N _____ Verify that fan assembly is free...

Страница 44: ...r Cat No 04 53547013 01 Edition Date 6 22 Printed in U S A Form No II547K 14 01 PRESSURES Refrigerant Suction ____________ PSIG Refrigerant Discharge ____________ PSIG Verify Refrigerant Charge using...

Отзывы: