![Bryant 581J Скачать руководство пользователя страница 25](http://html1.mh-extra.com/html/bryant/581j/581j_product-data_2822131025.webp)
25
SELECTION PROCEDURE (WITH 581J*07A EXAMPLE)
1
I.
Determine cooling and heating loads.
Given:
Mixed air dry bulb
80
_
F (27
_
C)
Mixed air wet bulb
67
_
F (19
_
C)
Ambient dry bulb
95
_
F (35
_
C)
TC
Load
73.6 MBH
SHC
Load
53.3 MBH
Vertical supply air
2100 CFM
Heating load
85.0 MBH
External static pressure
0.67 in. wg
Electrical characteristics
230--3--60
II.
Make an initial guess at cooling tons.
Refrig. tons = TC
Load
/ 12 MBH per ton
Refrig. tons = 72.0 / 12 = 6.0 tons
In this case, start by looking at the 581J**07.
III. Look up the rooftop’s TC and SHC.
Table 15 shows that, at the application’s supply air
CFM, mixed air and ambient temperatures, the
581J*A07 supplies:
TC = 73.6 MBH
2
SHC = 53.3 MBH
2
IV. Calculate the building latent heat load.
LC
Load
= TC
Load
-- SHC
Load
LC
Load
= 72.0 MBH -- 54.0 MBH = 18.0 MBH
V.
Calculate RTU latent heat capacity.
LC = TC -- SHC
LC = 73.6 MBH -- 53.3 MBH = 20.3 MBH
VI. Compare RTU capacities to loads.
3
Compare the rooftop’s SHC and LC to the
building’s sensible and latent heat loads.
VII. Select factory options (FIOP)
Local code requires an economizer for any unit with
TC greater than 65.0 MBH.
VIII. Calculate the total static pressure.
External static pressure
0.67 in. wg
Sum of FIOP / Accessory static
+0.13 in. wg
Total Static Pressure
0.80 in. wg
IX. Look up the indoor fan RPM & BHP.
Table 36 shows, at 2100 CFM & ESP= 0.8,
RPM = 712 & BHP = 1.17
X.
Convert BHP (Step VIII) into fan motor heat.
Fan motor heat = 2.546* BHP/Motor Eff.
4
Fan motor heat = 3.7 MBH
XI. Calculate RTU heating capacity.
Building heating load
85.0 MBH
Fan motor heat
--3.7 MBH
Required heating capacity
81.3 MBH
XII. Select a gas heater.
Table 4 shows the heating capacities of the
581JEA07 = 103.0 MBH. Select the 581JEA07
XIII. Determine electrical requirements.
Table 45 shows the MCA and Breaker Size of a
581J*A07 (without convenience outlet) as:
MCA = 32.0 amps & MOCP = 50.0 amps
Min. disconnect size: FLA = 31.0 & LRA = 148.
LEGEND
BHP
— Break horsepower
FLA
— Full load amps
LC
— Latent capacity
LRA
— Lock rotor amp
MBH
— (1,000) BTUH
MCA
— Min. circuit ampacity
MOCP — Max. over---current protection
RPM
— Revolutions per minute
RTU
— Rooftop unit
SHC
— Sensible heat capacity
TC
— Total capacity
NOTES
:
1. Selection software by Bryant saves time by performing
many of the steps above. Contact your Bryant sales
representative for assistance.
2. Unit ratings are gross capacities and do not include the
effect of evaporator fan motor heat. See Step XI. for de-
termining amount of evaporator fan motor heat to sub-
tract from total and sensible capacities to obtain net
cooling and net sensible capacities.
3. Selecting a unit with a SHC slightly lower than the
SHC
Load
is often better than oversizing. Slightly lower
SHC’s will help control indoor humidity, and prevent
temperature swings.
4. Indoor fan motor efficiency is available in Table 41. Use
the decimal form in the equation, eg. 80% = .8.
581J
Содержание 581J
Страница 51: ...51 TYPICAL WIRING DIAGRAMS C08518 Fig 15 1 Stage Cooling Typical Power Diagram 581J ...
Страница 52: ...52 TYPICAL WIRING DIAGRAMS cont C08577 Fig 16 2 Stage Cooling Typical Power Diagram 581J ...
Страница 53: ...53 C08524 Fig 17 1 Stage Typical Wiring Diagram 581J ...
Страница 54: ...54 C08578 Fig 18 2 Stage Typical Wiring Diagram 581J ...