![Bryant 581J Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/bryant/581j/581j_product-data_2822131015.webp)
15
TABLE 11 – PHYSICAL DATA
(HEATING)
7.5 -- 8.5 TONS
581J*08D
581J*09D
Gas Connection
# of Gas Valves
1
1
Nat. gas supply line press (in. w.g.)/(PSIG)
4 ---13 / 0.18 --- 0.47
4 ---13 / 0.18 --- 0.47
Propane supply line press (in. w.g.)/(PSIG)
11 ---13 / 0.40 --- 0.47
11 ---13 / 0.40 --- 0.47
Heat Anticipator Setting (Amps)
1st stage
0.14
0.14
2nd stage
0.14
0.14
Natural Gas, Propane Heat
# of stages / # of burners (total)
2 / 3
2 / 3
LO
W
Connection size
1/2” NPT
1/2” NPT
Rollout switch opens / closes
195 / 115
195 / 115
Temperature rise range (F)
20 --- 50
20 --- 50
# of stages / # of burners (total)
2 / 4
2 / 4
MED
Connection size
3/4” NPT
3/4” NPT
Rollout switch opens / closes
195 / 115
195 / 115
Temperature rise range (F)
35 --- 65
30 --- 65
# of stages / # of burners (total)
2 / 5
2 / 5
HI
G
H
Connection size
3/4” NPT
3/4” NPT
Rollout switch opens / closes
195 / 115
195 / 115
Temperature rise range (F)
45 --- 75
40 --- 75
581J