Bry-Air
VFB Dehumidifier
Set-up Sheet
Issue Date: October 2, 2014
Job Number: SGB:
202088
Dryer Size:
VFB-9-E-DX-P
Customer:
Blue Plains WWTP (Fluid Dynamics Inc.)
Installation:
Indoor
Desiccant:
Brysorb-Plus (Series ‘’N’’)
Process CFM:
900
Process Air Pressure Drop:
1.24
Inches w.c.
Reactivation CFM:
300
Reactivation Air Pressure Drop:
1.70
Inches w.c.
Reactivation High Temp. Limit Type/Setpoint
Manual Reset/ 350 deg F
Automatic Reset 325 deg F
Desiccant Bed Timing
Minutes/Revolution:
4m 12s
Revolutions/Hour
14.3
Design Conditions: Process Side of Unit
Process Air Inlet Dry Bulb Temperature (before coil)
75
deg F
Process Air Inlet Grains/Lb. (before coil)
86
gr.lb
Dehumidifier Air Inlet Dry Bulb Temperature (after coil)
49
deg F
Dehumidifier Air Inlet Grains/Lb. (after coil)
48
gr.lb
System Air Outlet Dry Bulb Temperature
94
deg F
System Air Outlet Grains/Lb.
10.5
gr.lb
Design Conditions: Reactivation Side of Unit
Reactivation Air Inlet Temperature Rise
205
deg F
Specialties:
Process Filter Pressure Switch
1.5
in. w.c.
React Filter Pressure Switch
1.5
in. w.c.