background image

 

  

 

 

 
 

 
 
 
 
 

 

 

 
 

 

Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England 

Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: [email protected] Web: www.broycecontrol.com

 

The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk

P9690-3-A

  6

6

6

6    

012375 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

ADDITONAL MEASUREMENTS 

 
With the 4-way connector wired and plugged in to the rear of the P9690, voltage 
and current present, it will be possible to measure and display the following 
information. 

 

1. VOLTAGE MEASUREMENTS 
    PHASE TO NEUTRAL OR PHASE TO PHASE 

The frequency measurement ”f” is derived from L1 and will therefore only appear 

on the LCD if L1 is present and the voltage is >12V phase to neutral. 

 

 

Quickly press the  

 button and the following will appear on the LCD 

which provides the phase to neutral measurements of the phases connected. 
The system measured frequency is also displayed. 

 

 
 
 
 
 
 

Screen example showing the phase to neutral voltages and frequency 

 

 

Press the same button again to display the measured phase to phase voltages.

 

 
 
 
 
 

 

Screen example showing the phase to phase voltages and frequency 

 

2. POWER 

The actual power displayed will also be dependant on the selected Toroid ratio’s. 

See examples on the right.

 

 

After viewing the phase to phase voltages, pressing the same button again 
displays the calculated power for each phase. 

 

 
 
 
 
 

 

3. POWER FACTOR 

By default, the displayed Power Factor will be 1.00.

 

 

After viewing the calculated power, pressing the same button again displays 
the calculated power factor for each phase. 

 

 
 
 
 
 

 

4. HOURS RUN 

This will run for as long as power is applied to the relay. 

The displayed time cannot be reset. 

The displayed time will be retained in memory during removal of power to the 

relay. 

 

 

After viewing the calculated power factor, pressing the same button again 
displays the hours run. 

 

 
 
 
 
 
 

 

Pressing the same button again will revert back to display the measured phase 
currents.

 

 
Notes 

    

If alterations to the User Settings are required whilst in one of the above screens, it 

will be necessary to exit first by pressing the  

 

briefly.

    

 
 
 
 
 

 

 

5. FAULT CONDITION 

 

 

If any of the examples shown on the left appear on the LCD, it will be exited 
automatically should a fault occur which initiates an Overcurrent or Earth fault 
time out.

 

 

The LCD will then revert to displaying which phase is at fault or whether the 
fault exists on the neutral. See “Tripping Modes” on the previous page.

 

 

6. EXAMPLES 

 

The following examples show the expected measured information based on the 
voltage and currents present at the inputs. Trip settings are not taken in to account 
in the examples. 
 
Example. 1 
 
VL1/L2/L3 = 228V, IL1/L2/L3 = 6.35A, f = 50Hz, CT ratio = 5:5 
 
 
 
 
 
 
                                    
 
 
 
 
 
 
Example. 2 
 
VL1/L2/L3 = 250V, IL1/L2/L3 = 1500A

1

, f = 50Hz, CT ratio = 2000:5 

 
 
 

 
 
 
 
 
 
 
 
 

1

 Current on the primary side of the externally connected 2000A CT’s 

 

V

L1/N

 

 

230.0

V

 

 

V

L2/N

 

 

230.0

V

 

   

V

L3

 /N

 

230.0

V

 

   

 

f

   

   

50.00

Hz

 

V

L1

 

     

400.0

V

 

 

V

L2

 

     

400.0

V

 

   

V

L3

 

     

400.0

V

 

   

 

f

   

   

50.00

Hz

 

P

L1/N

 

     

0.0

W

 

P

L2/N

 

     

0.0

W

 

   

P

L3/N

 

     

0.0

W

 

   

 

 

pf

L1/N

 

     

1.00 

pf

L2/N

 

     

1.00

 

 

pf

L3/N

 

     

1.00

 

   

 

 

 

  

HOURS RUN 

 

  

 

     

00000h 00m

 

 

 

 

 

V

L1/N

 

 

228.0

V

 

 

V

L2/N

 

 

228.0

V

 

   

V

L3

 /N

 

228.0

V

 

   

 

f

   

   

50.00

Hz

 

V

L1

 

     

395.0

V

 

 

V

L2

 

     

395.0

V

 

   

V

L3

 

     

395.0

V

 

   

 

f

   

   

50.00

Hz

 

P

L1/N

 

     

1.4

kW

 

P

L2/N

 

     

1.4

kW

 

   

P

L3/N

 

     

1.4

kW

 

   

 

 

pf

L1/N

 

     

1.00 

pf

L2/N

 

     

1.00

 

 

pf

L3/N

 

     

1.00

 

   

 

 

 

 

V

L1/N

 

 

250.0

V

 

 

V

L2/N

 

 

250.0

V

 

   

V

L3

 /N

 

250.0

V

 

   

 

f

   

   

50.00

Hz

 

V

L1

 

     

433.0

V

 

 

V

L2

 

     

433.0

V

 

   

V

L3

 

     

433.0

V

 

   

 

f

   

   

50.00

Hz

 

P

L1/N

 

   

375.0

kW

 

P

L2/N

 

   

375.0

kW

 

   

P

L3/N

 

   

375.0

kW

 

   

 

 

pf

L1/N

 

     

1.00 

pf

L2/N

 

     

1.00

 

 

pf

L3/N

 

     

1.00

 

   

 

 

 

 

Содержание P9690

Страница 1: ...o or Manual resetting Relay 2 has the added option of being allowed to energise at the start or end of a time out period If assigned to energise at the start the Relay can be used to operate a buzzer...

Страница 2: ...ccurred continued on next page INSTALLATION BEFORE INSTALLATION ISOLATE THE SUPPLY THIS PRODUCT IS DESIGNED TO CONNECT TO SEVERAL TYPES OF CIRCUITS ENSURE ALL ARE ISOLATED Remove the P9690 P9690 P9690...

Страница 3: ...TING Default setting for Relay 2 is linked to O C E F and energising at the end of the time out period Resetting mode is Auto Setting of Relay 2 is carried out in a similar manner as Relay 1 however i...

Страница 4: ...urther button presses are made If a trip condition occurs whilst in this mode the screen will automatically change to display the information relating to the current status As described in Section 8 u...

Страница 5: ...IO 0 00A Phase with fault 2 EARTH FAULT When an Earth fault occurs causing a flow in current through the Neutral an increase in current reading on the LCD will occur When the level of current exceeds...

Страница 6: ...tor for each phase 4 HOURS RUN This will run for as long as power is applied to the relay The displayed time cannot be reset The displayed time will be retained in memory during removal of power to th...

Страница 7: ...0 01 t t t t s s s s Normal Inverse Normal Inverse Normal Inverse Normal Inverse 3 10 3 10 3 10 3 10 NI NI NI NI 3 10 3 10 3 10 3 10 t t t t s s s s k k k k 1 0 0 9 0 8 0 7 0 6 0 5 0 4 0 3 0 2 0 1 0 0...

Страница 8: ...CHNICAL SPECIFICATION Aux Supply voltage Un 1 2 85 265VAC 85 370VDC1 18 55VAC 18 72VDC Voltage range should be specified at time of ordering Rated frequency 50 60Hz AC Supplies Isolation Over voltage...

Отзывы: