TRIPPING MODES 

 

1. OVERCURRENT 

 

 

A fault which develops on a phase will be indicated by an increase in current 
reading on the LCD. When the level of current exceeds the Low-set setting, 
the phase at fault will be highlighted by the digits flashing.

 

 

The LCD backlight will flash.

 

 

Relay 2 will energise if assigned to Overcurrent and set to energise at the start 
of the time out period (See Section 3. RELAY 2 SETTING).

 

 

The characters “I>” will display to indicate the Low-set has been triggered.

 

 
 
 

 

 
 
 
 
 
 
 
 
 
 
 

 

If the current continues to increase above the High-set setting, the

 

characters 

“I>”

 will change and display 

“I>>”

 to indicate the High-set has been 

triggered. 

 

 
 
 
 
 

 

When the unit finally trips, the digits of the phase at fault will stop flashing and 
remain highlighted. This allows the user to see which phase was at fault and 
caused the unit to trip.

 

 

The red “Tripped”

“Tripped”

“Tripped”

“Tripped” LED will also flash.

 

 

The relays which energised are also displayed on the screen after tripping.

 

 

Press 

to reset and return the unit back to normal operation (assuming 

the fault has been cleared). The LCD reverts back to displaying the normal 
system currents and the red “Tripped”

“Tripped”

“Tripped”

“Tripped” LED stops flashing.

 

 

If either relay is set for Auto resetting, then they would have de-energised after the 

fault had cleared. The corresponding relay ident (i.e. R1 and/or R2) on the display 
would also disappear. Pressing the “RESET” 

“RESET” 

“RESET” 

“RESET” button will only clear the LCD. If either 

relay is set for Manual resetting, then pressing the “RESET”

“RESET”

“RESET”

“RESET” button will de-energise the 

relay(s) and clear the LCD.

 

 

In the event of an Overcurrent condition, the basic sequence of events is 
shown below. 

Assuming High-set trip is enabled.

 

 

I

L1

 

 

20.70

A

    

I> 

I

L2

 

 

40.00

A    

 

I

L3

 

 

27.50

A  

 

I

O

 

  

0.00

A    

 

Phase with fault

 

2. EARTH FAULT 

 

 

When an Earth fault occurs causing a flow in current through the Neutral, an 
increase in current reading on the LCD will occur. When the level of current 
exceeds the Low-set setting, the reading will be highlighted by the digits 
flashing.

 

 

The LCD backlight will flash.

 

 

Relay 2 will energise if assigned to Earth fault and set to energise at the start of 
the time out period (See Section 3. RELAY 2 SETTING).

 

 

The characters 

“Io>”

 will display to indicate the Low-set has been triggered. 

 

 
 
 
 
 
 

 

If the current continues to increase above the High-set setting, the

 

characters 

“Io>”

 will change and display 

“Io>>”

 to indicate the High-set has been 

triggered. 

 

 
 
 
 
 
 
 
 

 

When the unit finally trips, the digits will stop flashing and remain highlighted. 
This allows the user to see what caused the unit to trip.

 

 

The red “Tripped”

“Tripped”

“Tripped”

“Tripped” LED will also flash.

 

 

The relays which energised are also displayed on the screen after tripping.

 

 

Press 

to reset and return the unit back to normal operation (assuming 

the fault has been cleared). The LCD reverts back to displaying the normal 
system currents and the red “Tripped”

“Tripped”

“Tripped”

“Tripped” LED stops flashing.

 

 

 If either relay is set for Auto resetting, then they would have de-energised after the 

fault had cleared. The corresponding relay ident (i.e. R1 and/or R2) on the display 
would also disappear.  Pressing the “RESET”

“RESET”

“RESET”

“RESET” button will only clear the LCD. If either 

relay is set for Manual resetting, then pressing the “RESET”

“RESET”

“RESET”

“RESET” button will de-energise the 

relay(s) and clear the LCD. 
 

In the event of an Earth fault condition, the basic sequence of events is shown 
below. 

Assuming High-set trip is enabled.

 

 

 

I

L1

 

 

20.70

A

    

I>> 

I

L2

 

 

89.00

A    

R1    R2

 

I

L3

 

 

27.50

A  

 

I

O

  

   

0.00

A

 

I

L1

 

 

0.00

A

  

 

I

L2

 

 

0.00

A

      

 

I

L3

 

 

0.00

A    

Io>

 

I

O

 

  

1.00

   

 

I

L1

 

 

0.00

A

  

 

I

L2

 

 

0.00

A

    

 

I

L3

 

 

0.00

A    

Io>>

 

I

O

 

  

8.00

    R1 

 

Low-set  
triggered 
 

High-set 
triggered 

 

Relay(s) which 
energised on 
tripping

 

Low-set 
triggered

 

High-set 
triggered 
 
Relay(s) which 
energised on 
tripping

 

    

Earth fault 

current

 

OVERCURRENT 

fault occurs 

Low-set I> 

triggered

 

Run IDMT or DT 

delay t> 

Run DT delay 

t>>

 

High-set 

I>> 

triggered? 

TRIP! 

Delay 

t> 

complete? 

Delay 

t>> 

complete? 

START 

EARTH FAULT 

occurs 

Low-set I

o

triggered

 

Run IDMT or DT 

delay t

o

Run DT delay 

t

o

>>

 

High-set 

I

o

>> 

triggered? 

TRIP! 

Delay 

t

o

complete? 

Delay 
t

o

>> 

complete? 

START 

Содержание P9690

Страница 1: ...o or Manual resetting Relay 2 has the added option of being allowed to energise at the start or end of a time out period If assigned to energise at the start the Relay can be used to operate a buzzer...

Страница 2: ...ccurred continued on next page INSTALLATION BEFORE INSTALLATION ISOLATE THE SUPPLY THIS PRODUCT IS DESIGNED TO CONNECT TO SEVERAL TYPES OF CIRCUITS ENSURE ALL ARE ISOLATED Remove the P9690 P9690 P9690...

Страница 3: ...TING Default setting for Relay 2 is linked to O C E F and energising at the end of the time out period Resetting mode is Auto Setting of Relay 2 is carried out in a similar manner as Relay 1 however i...

Страница 4: ...urther button presses are made If a trip condition occurs whilst in this mode the screen will automatically change to display the information relating to the current status As described in Section 8 u...

Страница 5: ...IO 0 00A Phase with fault 2 EARTH FAULT When an Earth fault occurs causing a flow in current through the Neutral an increase in current reading on the LCD will occur When the level of current exceeds...